OpenStudio Results
Model Summary
| Information | Value | Units |
|---|---|---|
| Building Name | 90.1-2010-SmallHotel-ASHRAE 169-2006-5B created: 2016-10-04 13:28:55 -0600 | building_name |
| Net Site Energy | 3,509,852 | kBtu |
| Total Building Area | 43,202 | ft^2 |
| EUI (Based on Net Site Energy and Total Building Area) | 81.24 | kBtu/ft^2 |
| OpenStudio Standards Building Type | SmallHotel |
| Value | |
|---|---|
| Weather File | Denver Centennial Golden Nr CO USA TMY3 WMO#=724666 |
| Latitude | 39.74 |
| Longitude | -105.2 |
| Elevation | 6001 (ft) |
| Time Zone | -7.0 |
| North Axis Angle | 180.00 |
| ASHRAE Climate Zone | 5B |
| Maximum Dry Bulb (F) | Daily Temperature Range (R) | Humidity Value | Humidity Type | Wind Speed (mph) | Wind Direction | |
|---|---|---|---|---|---|---|
| DENVER CENTENNIAL GOLDEN N ANN CLG .4% CONDNS DB=>MWB | 91.4 | 27.36 | 60.26 | Wetbulb [F] | 10.96 | 0.0 |
| DENVER CENTENNIAL GOLDEN N ANN CLG .4% CONDNS DP=>MDB | 68.36 | 27.36 | 60.98 | Dewpoint [F] | 10.96 | 0.0 |
| DENVER CENTENNIAL GOLDEN N ANN CLG .4% CONDNS ENTH=>MDB | 81.14 | 27.36 | 25.67 | Enthalpy [Btu/lb] | 10.96 | 0.0 |
| DENVER CENTENNIAL GOLDEN N ANN CLG .4% CONDNS WB=>MDB | 81.14 | 27.36 | 65.12 | Wetbulb [F] | 10.96 | 0.0 |
| DENVER CENTENNIAL GOLDEN N ANN HTG 99.6% CONDNS DB | -1.84 | 0.0 | -1.84 | Wetbulb [F] | 6.71 | 340.0 |
| DENVER CENTENNIAL GOLDEN N ANN HTG WIND 99.6% CONDNS WS=>MCDB | 39.02 | 0.0 | 39.02 | Wetbulb [F] | 27.29 | 340.0 |
| DENVER CENTENNIAL GOLDEN N ANN HUM_N 99.6% CONDNS DP=>MCDB | 12.38 | 0.0 | -6.88 | Dewpoint [F] | 6.71 | 340.0 |
| Time Setpoint Not Met | Time (hr) |
|---|---|
| During Heating | 954.25 |
| During Cooling | 3233.5 |
| During Occupied Heating | 722.5 |
| During Occupied Cooling | 637.75 |
| Tolerance for Time Setpoint Not Met | Temperature (F) |
|---|---|
| Heating | 0.36 |
| Cooling | 0.36 |
Annual Overview
| End Use | Consumption (kBtu) |
|---|---|
| Heating | 175,867 |
| Cooling | 372,947 |
| Interior Lighting | 362,227 |
| Exterior Lighting | 62,319 |
| Interior Equipment | 959,352 |
| Exterior Equipment | 0 |
| Fans | 977,086 |
| Pumps | 246 |
| Heat Rejection | 0 |
| Humidification | 0 |
| Heat Recovery | 0 |
| Water Systems | 599,807 |
| Refrigeration | 0 |
| Generators | 0 |
| Fuel | Consumption (kBtu) |
|---|---|
| Electricity | 2,410,261 |
| Natural Gas | 1,099,591 |
| Additional Fuel | 0 |
| District Cooling | 0 |
| District Heating | 0 |
| End Use | Consumption (kWh) |
|---|---|
| Heating | 22,128 |
| Cooling | 109,300 |
| Interior Lighting | 106,158 |
| Exterior Lighting | 18,264 |
| Interior Equipment | 164,103 |
| Exterior Equipment | 0 |
| Fans | 286,356 |
| Pumps | 72 |
| Heat Rejection | 0 |
| Humidification | 0 |
| Heat Recovery | 0 |
| Water Systems | 0 |
| Refrigeration | 0 |
| Generators | 0 |
| End Use | Consumption (therms) |
|---|---|
| Heating | 1,004 |
| Cooling | 0 |
| Interior Lighting | 0 |
| Exterior Lighting | 0 |
| Interior Equipment | 3,995 |
| Exterior Equipment | 0 |
| Fans | 0 |
| Pumps | 0 |
| Heat Rejection | 0 |
| Humidification | 0 |
| Heat Recovery | 0 |
| Water Systems | 5,999 |
| Refrigeration | 0 |
| Generators | 0 |
Monthly Overview
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | Total | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Heating | 4000.14 | 4889.61 | 3293.28 | 786.2 | 251.73 | 3.21 | 3.21 | 0.59 | 27.19 | 547.7 | 3172.19 | 5152.61 | 22127.65 |
| Cooling | 4766.36 | 3795.17 | 5966.58 | 7622.31 | 10201.11 | 13901.58 | 15886.56 | 16169.39 | 12408.25 | 8442.72 | 5531.31 | 4609.47 | 109300.81 |
| Interior Lighting | 9043.28 | 8157.94 | 9008.28 | 8733.28 | 8982.08 | 8684.25 | 9008.78 | 8986.75 | 8727.83 | 9028.17 | 8742.44 | 9054.03 | 106157.11 |
| Exterior Lighting | 1876.23 | 1579.92 | 1586.21 | 1371.57 | 1274.2 | 1162.17 | 1232.32 | 1351.68 | 1464.75 | 1684.62 | 1773.62 | 1905.54 | 18262.82 |
| Interior Equipment | 13937.5 | 12588.83 | 13938.42 | 13486.75 | 13938.42 | 13488.56 | 13936.61 | 13938.42 | 13487.64 | 13937.5 | 13488.56 | 13936.61 | 164103.81 |
| Exterior Equipment | |||||||||||||
| Fans | 24320.56 | 21966.94 | 24320.56 | 23536.03 | 24320.56 | 23536.03 | 24320.56 | 24320.56 | 23536.03 | 24320.56 | 23536.03 | 24320.56 | 286354.94 |
| Pumps | 6.05 | 5.46 | 6.05 | 5.85 | 6.05 | 5.85 | 6.05 | 6.05 | 5.85 | 6.05 | 5.85 | 6.05 | 71.21 |
| Heat Rejection | |||||||||||||
| Humidification | |||||||||||||
| Heat Recovery | |||||||||||||
| Water Systems | |||||||||||||
| Refrigeration | |||||||||||||
| Generators | |||||||||||||
| Total | 57950.11 | 52983.88 | 58119.36 | 55541.98 | 58974.14 | 60781.65 | 64394.07 | 64773.42 | 59657.55 | 57967.32 | 56250.0 | 58984.86 | 706378.35 |
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | Total | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Heating | 17.23 | 19.43 | 15.1 | 6.67 | 3.2 | 0.28 | 0.06 | 0.01 | 0.79 | 5.4 | 14.24 | 17.97 | 100.37 |
| Cooling | |||||||||||||
| Interior Lighting | |||||||||||||
| Exterior Lighting | |||||||||||||
| Interior Equipment | 33.92 | 30.64 | 33.92 | 32.83 | 33.92 | 32.83 | 33.92 | 33.92 | 32.83 | 33.92 | 32.83 | 33.92 | 399.41 |
| Exterior Equipment | |||||||||||||
| Fans | |||||||||||||
| Pumps | |||||||||||||
| Heat Rejection | |||||||||||||
| Humidification | |||||||||||||
| Heat Recovery | |||||||||||||
| Water Systems | 56.99 | 52.09 | 56.62 | 52.26 | 50.64 | 45.78 | 44.95 | 44.26 | 43.88 | 47.96 | 49.72 | 54.66 | 599.81 |
| Refrigeration | |||||||||||||
| Generators | |||||||||||||
| Total | 108.14 | 102.15 | 105.64 | 91.76 | 87.76 | 78.89 | 78.94 | 78.2 | 77.49 | 87.28 | 96.79 | 106.54 | 1099.59 |
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Heating | 41.9297 | 61.2431 | 45.1227 | 18.7883 | 35.292 | 60.1593 | ||||||
| Cooling | 1.53 | 0.8214 | 1.2945 | 6.3242 | 22.7161 | 29.02 | 29.749 | 31.7402 | 27.993 | 19.0066 | 2.4658 | 0.8328 |
| Interior Lighting | 14.0887 | 14.0887 | 14.0887 | 14.0116 | 16.3549 | 16.2522 | 16.4063 | 16.3549 | 16.4063 | 16.4577 | 14.0887 | 14.0887 |
| Exterior Lighting | 4.188 | 4.188 | ||||||||||
| Interior Equipment | 39.3371 | 39.3371 | 39.3371 | 39.3371 | 43.1723 | 43.1723 | 43.1723 | 43.1723 | 43.1723 | 43.1723 | 39.3371 | 39.3371 |
| Exterior Equipment | ||||||||||||
| Fans | 32.6889 | 32.6889 | 32.6889 | 32.6889 | 32.6889 | 32.6889 | 32.6889 | 32.6889 | 32.6889 | 32.6889 | 32.6889 | 32.6889 |
| Pumps | 0.0081 | 0.0081 | 0.0081 | 0.0081 | 0.0081 | 0.0081 | 0.0081 | 0.0081 | 0.0081 | 0.0081 | 0.0081 | 0.0081 |
| Heat Rejection | ||||||||||||
| Humidification | ||||||||||||
| Heat Recovery | ||||||||||||
| Water Systems | ||||||||||||
| Refrigeration | ||||||||||||
| Generators | ||||||||||||
| Total | 133.77 | 148.19 | 132.54 | 111.16 | 114.94 | 121.14 | 122.02 | 123.96 | 120.27 | 111.33 | 123.88 | 151.3 |
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Heating | 3.7989 | 56.133 | 3.9318 | 13.1122 | 16.1516 | 40.4085 | 65.5851 | |||||
| Cooling | ||||||||||||
| Interior Lighting | ||||||||||||
| Exterior Lighting | ||||||||||||
| Interior Equipment | 136.7847 | 136.7847 | 136.7847 | 136.7847 | 136.7847 | 136.7847 | 136.7847 | 136.7847 | 136.7847 | 136.7847 | 136.7847 | 136.7847 |
| Exterior Equipment | ||||||||||||
| Fans | ||||||||||||
| Pumps | ||||||||||||
| Heat Rejection | ||||||||||||
| Humidification | ||||||||||||
| Heat Recovery | ||||||||||||
| Water Systems | 209.3749 | 175.028 | 214.7991 | 208.0622 | 158.3366 | 149.6527 | 144.4346 | 143.104 | 145.1642 | 150.3219 | 159.9724 | 164.9601 |
| Refrigeration | ||||||||||||
| Generators | ||||||||||||
| Total | 349.96 | 367.95 | 355.52 | 344.85 | 308.23 | 286.44 | 281.22 | 279.89 | 281.95 | 303.26 | 337.17 | 367.33 |
Utility Bills/Rates
No Data to Show for Utility Bills/Rates
Envelope
| Construction | Net Area (ft^2) | Surface Count | R Value (ft^2*h*R/Btu) |
|---|---|---|---|
| Typical IEAD Roof R-20.83 | 10,800 | 16 | 20.05 |
| Typical Insulated Steel Framed Exterior Wall R-15.63 | 16,258 | 92 | 14.78 |
| Construction | Area (ft^2) | Surface Count | U-Factor (Btu/ft^2*h*R) |
|---|---|---|---|
| U 0.52 SHGC 0.40 Dbl Ref-D Clr 6mm/13mm Air | 1,983 | 103 |
| Description | Total (%) | North (%) | East (%) | South (%) | West (%) |
|---|---|---|---|---|---|
| Gross Window-Wall Ratio | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
| Gross Window-Wall Ratio (Conditioned) | 12.01 | 15.95 | 3.95 | 12.11 | 5.68 |
| Skylight-Roof Ratio | 0.0 |
Space Type Breakdown
| Space Type Name | Floor Area (ft^2) | Standards Building Type | Standards Space Type |
|---|---|---|---|
| SmallHotel Corridor | 4,320 | SmallHotel | Corridor |
| SmallHotel Corridor4 | 1,350 | SmallHotel | Corridor4 |
| SmallHotel Elec/MechRoom | 162 | SmallHotel | Elec/MechRoom |
| SmallHotel ElevatorCore | 324 | SmallHotel | ElevatorCore |
| SmallHotel ElevatorCore4 | 162 | SmallHotel | ElevatorCore4 |
| SmallHotel Exercise | 351 | SmallHotel | Exercise |
| SmallHotel GuestLounge | 1,755 | SmallHotel | GuestLounge |
| SmallHotel GuestRoom123Occ | 12,366 | SmallHotel | GuestRoom123Occ |
| SmallHotel GuestRoom123Vac | 6,399 | SmallHotel | GuestRoom123Vac |
| SmallHotel GuestRoom4Occ | 5,265 | SmallHotel | GuestRoom4Occ |
| SmallHotel GuestRoom4Vac | 3,240 | SmallHotel | GuestRoom4Vac |
| SmallHotel Laundry | 1,053 | SmallHotel | Laundry |
| SmallHotel Mechanical | 351 | SmallHotel | Mechanical |
| SmallHotel Meeting | 864 | SmallHotel | Meeting |
| SmallHotel Office | 1,404 | SmallHotel | Office |
| SmallHotel PublicRestroom | 351 | SmallHotel | PublicRestroom |
| SmallHotel StaffLounge | 351 | SmallHotel | StaffLounge |
| SmallHotel Stair | 1,296 | SmallHotel | Stair |
| SmallHotel Stair4 | 432 | SmallHotel | Stair4 |
| SmallHotel Storage | 1,053 | SmallHotel | Storage |
| SmallHotel Storage4Front | 135 | SmallHotel | Storage4Front |
| SmallHotel Storage4Rear | 216 | SmallHotel | Storage4Rear |
Space Type Summary
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| SmallHotel Corridor Lights Definition | 0.6600 | W/ft^2 | 1.0 |
| SmallHotel Corridor Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| SmallHotel Corridor4 Lights Definition | 0.6600 | W/ft^2 | 1.0 |
| SmallHotel Corridor4 Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| SmallHotel Elec/MechRoom Elec Equip Definition | 198.2000 | W/ft^2 | 1.0 |
| SmallHotel Elec/MechRoom Ventilation (outdoor air method Sum) | 0.1200 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| SmallHotel ElevatorCore Ventilation (outdoor air method Sum) | 0.1200 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| SmallHotel ElevatorCore4 Ventilation (outdoor air method Sum) | 0.1200 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| SmallHotel Exercise People Definition | 0.0199 | people/ft^2 | 1.0 |
| SmallHotel Exercise Elec Equip Definition | 1.7300 | W/ft^2 | 1.0 |
| SmallHotel Exercise Lights Definition | 0.7200 | W/ft^2 | 1.0 |
| SmallHotel Exercise Ventilation (outdoor air method Sum) | 20.0000 | cfm/person | |
| SmallHotel Exercise Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| SmallHotel GuestLounge People Definition | 0.0300 | people/ft^2 | 1.0 |
| SmallHotel GuestLounge Elec Equip Definition | 2.4200 | W/ft^2 | 1.0 |
| SmallHotel GuestLounge Lights Definition | 0.7300 | W/ft^2 | 1.0 |
| SmallHotel GuestLounge Ventilation (outdoor air method Sum) | 7.5000 | cfm/person | |
| SmallHotel GuestLounge Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| SmallHotel GuestRoom123Occ People Definition | 0.0043 | people/ft^2 | 1.0 |
| SmallHotel GuestRoom123Occ Elec Equip Definition | 1.1000 | W/ft^2 | 1.0 |
| SmallHotel GuestRoom123Occ Lights Definition | 0.7500 | W/ft^2 | 1.0 |
| SmallHotel GuestRoom123Occ Ventilation (outdoor air method Sum) | 5.0000 | cfm/person | |
| SmallHotel GuestRoom123Occ Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| SmallHotel GuestRoom123Vac People Definition | 0.0043 | people/ft^2 | 1.0 |
| SmallHotel GuestRoom123Vac Elec Equip Definition | 1.1000 | W/ft^2 | 1.0 |
| SmallHotel GuestRoom123Vac Lights Definition | 0.7500 | W/ft^2 | 1.0 |
| SmallHotel GuestRoom123Vac Ventilation (outdoor air method Sum) | 5.0000 | cfm/person | |
| SmallHotel GuestRoom123Vac Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| SmallHotel GuestRoom4Occ People Definition | 0.0043 | people/ft^2 | 1.0 |
| SmallHotel GuestRoom4Occ Elec Equip Definition | 1.1000 | W/ft^2 | 1.0 |
| SmallHotel GuestRoom4Occ Lights Definition | 0.7500 | W/ft^2 | 1.0 |
| SmallHotel GuestRoom4Occ Ventilation (outdoor air method Sum) | 5.0000 | cfm/person | |
| SmallHotel GuestRoom4Occ Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| SmallHotel GuestRoom4Vac People Definition | 0.0043 | people/ft^2 | 1.0 |
| SmallHotel GuestRoom4Vac Elec Equip Definition | 1.1000 | W/ft^2 | 1.0 |
| SmallHotel GuestRoom4Vac Lights Definition | 0.7500 | W/ft^2 | 1.0 |
| SmallHotel GuestRoom4Vac Ventilation (outdoor air method Sum) | 5.0000 | cfm/person | |
| SmallHotel GuestRoom4Vac Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| SmallHotel Laundry People Definition | 0.0100 | people/ft^2 | 1.0 |
| SmallHotel Laundry Elec Equip Definition | 2.5700 | W/ft^2 | 1.0 |
| SmallHotel Laundry Gas Equip Definition | 38.0699 | W/ft^2 | 1.0 |
| SmallHotel Laundry Lights Definition | 0.6000 | W/ft^2 | 1.0 |
| SmallHotel Laundry Ventilation (outdoor air method Sum) | 7.5000 | cfm/person | |
| SmallHotel Laundry Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| SmallHotel Mechanical Lights Definition | 0.9500 | W/ft^2 | 1.0 |
| SmallHotel Mechanical Ventilation (outdoor air method Sum) | 0.1200 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| SmallHotel Meeting People Definition | 0.0500 | people/ft^2 | 1.0 |
| SmallHotel Meeting Elec Equip Definition | 0.5740 | W/ft^2 | 1.0 |
| SmallHotel Meeting Lights Definition | 1.2300 | W/ft^2 | 1.0 |
| SmallHotel Meeting Ventilation (outdoor air method Sum) | 5.0000 | cfm/person | |
| SmallHotel Meeting Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| SmallHotel Office People Definition | 0.0071 | people/ft^2 | 1.0 |
| SmallHotel Office Elec Equip Definition | 1.2800 | W/ft^2 | 1.0 |
| SmallHotel Office Lights Definition | 1.1100 | W/ft^2 | 1.0 |
| SmallHotel Office Ventilation (outdoor air method Sum) | 5.0000 | cfm/person | |
| SmallHotel Office Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| SmallHotel PublicRestroom People Definition | 0.0028 | people/ft^2 | 1.0 |
| SmallHotel PublicRestroom Lights Definition | 0.9800 | W/ft^2 | 1.0 |
| SmallHotel PublicRestroom Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| SmallHotel StaffLounge People Definition | 0.0513 | people/ft^2 | 1.0 |
| SmallHotel StaffLounge Elec Equip Definition | 2.0000 | W/ft^2 | 1.0 |
| SmallHotel StaffLounge Lights Definition | 0.7300 | W/ft^2 | 1.0 |
| SmallHotel StaffLounge Ventilation (outdoor air method Sum) | 7.5000 | cfm/person | |
| SmallHotel StaffLounge Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| SmallHotel Stair Lights Definition | 0.6900 | W/ft^2 | 1.0 |
| SmallHotel Stair Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| SmallHotel Stair4 Lights Definition | 0.6900 | W/ft^2 | 1.0 |
| SmallHotel Stair4 Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| SmallHotel Storage Lights Definition | 0.6300 | W/ft^2 | 1.0 |
| SmallHotel Storage Ventilation (outdoor air method Sum) | 0.1200 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| SmallHotel Storage4Front Lights Definition | 0.6300 | W/ft^2 | 1.0 |
| SmallHotel Storage4Front Ventilation (outdoor air method Sum) | 0.1200 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| SmallHotel Storage4Rear Lights Definition | 0.6300 | W/ft^2 | 1.0 |
| SmallHotel Storage4Rear Ventilation (outdoor air method Sum) | 0.1200 | cfm/floor area ft^2 |
Interior Lighting Summary
| Zone | Lighting Power Density (W/ft^2) | Total Power (W) | Schedule Name | Scheduled Hours/Week (hr) | Actual Load Hours/Week (hr) | Return Air Fraction | Annual Consumption (kWh) | |
|---|---|---|---|---|---|---|---|---|
| CORRIDORFLR1 ZN SMALLHOTEL CORRIDOR LIGHTS | CORRIDORFLR1 ZN | 0.66 | 1069.22 | HOTELSMALL BLDG_LIGHT_CORRIDOR_SCH | 168.0 | 168.0 | 0.0000 | 9366.67 |
| CORRIDORFLR2 ZN SMALLHOTEL CORRIDOR LIGHTS | CORRIDORFLR2 ZN | 0.66 | 891.01 | HOTELSMALL BLDG_LIGHT_CORRIDOR_SCH | 168.0 | 168.0 | 0.0000 | 7805.56 |
| CORRIDORFLR3 ZN SMALLHOTEL CORRIDOR LIGHTS | CORRIDORFLR3 ZN | 0.66 | 891.01 | HOTELSMALL BLDG_LIGHT_CORRIDOR_SCH | 168.0 | 168.0 | 0.0000 | 7805.56 |
| CORRIDORFLR4 ZN SMALLHOTEL CORRIDOR4 LIGHTS | CORRIDORFLR4 ZN | 0.66 | 891.01 | HOTELSMALL BLDG_LIGHT_CORRIDOR_SCH | 168.0 | 168.0 | 0.0000 | 7805.56 |
| EXERCISECENTERFLR1 ZN SMALLHOTEL EXERCISE LIGHTS | EXERCISECENTERFLR1 ZN | 0.72 | 252.72 | HOTELSMALL BLDG_LIGHT_EXERCENTER_SCH | 112.0 | 112.0 | 0.0000 | 1475.0 |
| FRONTLOUNGEFLR1 ZN SMALLHOTEL GUESTLOUNGE LIGHTS | FRONTLOUNGEFLR1 ZN | 0.73 | 1281.24 | HOTELSMALL BLDG_LIGHT_FRONTLOUNGE_SCH | 84.35 | 76.69 | 0.0000 | 5122.22 |
| GUESTROOM103 ZN SMALLHOTEL GUESTROOM123OCC LIGHTS | GUESTROOM103 ZN | 0.75 | 263.27 | HOTELSMALL BLDG_LIGHT_GUESTROOM_SCH_2010 | 60.84 | 60.84 | 0.0000 | 836.11 |
| GUESTROOM104 ZN SMALLHOTEL GUESTROOM123OCC LIGHTS | GUESTROOM104 ZN | 0.75 | 263.25 | HOTELSMALL BLDG_LIGHT_GUESTROOM_SCH_2010 | 60.84 | 60.84 | 0.0000 | 836.11 |
| GUESTROOM105 ZN SMALLHOTEL GUESTROOM123OCC LIGHTS | GUESTROOM105 ZN | 0.75 | 263.25 | HOTELSMALL BLDG_LIGHT_GUESTROOM_SCH_2010 | 60.84 | 60.84 | 0.0000 | 836.11 |
| GUESTROOM202_205 ZN SMALLHOTEL GUESTROOM123OCC LIGHTS | GUESTROOM202_205 ZN | 0.75 | 1053.07 | HOTELSMALL BLDG_LIGHT_GUESTROOM_SCH_2010 | 60.84 | 60.84 | 0.0000 | 3341.67 |
| GUESTROOM206_208 ZN SMALLHOTEL GUESTROOM123OCC LIGHTS | GUESTROOM206_208 ZN | 0.75 | 850.56 | HOTELSMALL BLDG_LIGHT_GUESTROOM_SCH_2010 | 60.84 | 60.84 | 0.0000 | 2697.22 |
| GUESTROOM209_212 ZN SMALLHOTEL GUESTROOM123OCC LIGHTS | GUESTROOM209_212 ZN | 0.75 | 1053.07 | HOTELSMALL BLDG_LIGHT_GUESTROOM_SCH_2010 | 60.84 | 60.84 | 0.0000 | 3341.67 |
| GUESTROOM213 ZN SMALLHOTEL GUESTROOM123OCC LIGHTS | GUESTROOM213 ZN | 0.75 | 263.27 | HOTELSMALL BLDG_LIGHT_GUESTROOM_SCH_2010 | 60.84 | 60.84 | 0.0000 | 836.11 |
| GUESTROOM214 ZN SMALLHOTEL GUESTROOM123OCC LIGHTS | GUESTROOM214 ZN | 0.75 | 263.25 | HOTELSMALL BLDG_LIGHT_GUESTROOM_SCH_2010 | 60.84 | 60.84 | 0.0000 | 836.11 |
| GUESTROOM219 ZN SMALLHOTEL GUESTROOM123OCC LIGHTS | GUESTROOM219 ZN | 0.75 | 263.25 | HOTELSMALL BLDG_LIGHT_GUESTROOM_SCH_2010 | 60.84 | 60.84 | 0.0000 | 836.11 |
| GUESTROOM220_223 ZN SMALLHOTEL GUESTROOM123OCC LIGHTS | GUESTROOM220_223 ZN | 0.75 | 1053.0 | HOTELSMALL BLDG_LIGHT_GUESTROOM_SCH_2010 | 60.84 | 60.84 | 0.0000 | 3338.89 |
| GUESTROOM224 ZN SMALLHOTEL GUESTROOM123OCC LIGHTS | GUESTROOM224 ZN | 0.75 | 263.25 | HOTELSMALL BLDG_LIGHT_GUESTROOM_SCH_2010 | 60.84 | 60.84 | 0.0000 | 836.11 |
| GUESTROOM309_312 ZN SMALLHOTEL GUESTROOM123OCC LIGHTS | GUESTROOM309_312 ZN | 0.75 | 1053.07 | HOTELSMALL BLDG_LIGHT_GUESTROOM_SCH_2010 | 60.84 | 60.84 | 0.0000 | 3341.67 |
| GUESTROOM314 ZN SMALLHOTEL GUESTROOM123OCC LIGHTS | GUESTROOM314 ZN | 0.75 | 263.25 | HOTELSMALL BLDG_LIGHT_GUESTROOM_SCH_2010 | 60.84 | 60.84 | 0.0000 | 836.11 |
| GUESTROOM315_318 ZN SMALLHOTEL GUESTROOM123OCC LIGHTS | GUESTROOM315_318 ZN | 0.75 | 1053.0 | HOTELSMALL BLDG_LIGHT_GUESTROOM_SCH_2010 | 60.84 | 60.84 | 0.0000 | 3338.89 |
| GUESTROOM320_323 ZN SMALLHOTEL GUESTROOM123OCC LIGHTS | GUESTROOM320_323 ZN | 0.75 | 1053.0 | HOTELSMALL BLDG_LIGHT_GUESTROOM_SCH_2010 | 60.84 | 60.84 | 0.0000 | 3338.89 |
| GUESTROOM101 ZN SMALLHOTEL GUESTROOM123VAC LIGHTS | GUESTROOM101 ZN | 0.75 | 263.27 | HOTELSMALL ALWAYSOFF | 0.0 | 0.0 | 0.0000 | 0.0 |
| GUESTROOM102 ZN SMALLHOTEL GUESTROOM123VAC LIGHTS | GUESTROOM102 ZN | 0.75 | 263.27 | HOTELSMALL ALWAYSOFF | 0.0 | 0.0 | 0.0000 | 0.0 |
| GUESTROOM201 ZN SMALLHOTEL GUESTROOM123VAC LIGHTS | GUESTROOM201 ZN | 0.75 | 263.27 | HOTELSMALL ALWAYSOFF | 0.0 | 0.0 | 0.0000 | 0.0 |
| GUESTROOM215_218 ZN SMALLHOTEL GUESTROOM123VAC LIGHTS | GUESTROOM215_218 ZN | 0.75 | 1053.0 | HOTELSMALL ALWAYSOFF | 0.0 | 0.0 | 0.0000 | 0.0 |
| GUESTROOM301 ZN SMALLHOTEL GUESTROOM123VAC LIGHTS | GUESTROOM301 ZN | 0.75 | 263.27 | HOTELSMALL ALWAYSOFF | 0.0 | 0.0 | 0.0000 | 0.0 |
| GUESTROOM302_305 ZN SMALLHOTEL GUESTROOM123VAC LIGHTS | GUESTROOM302_305 ZN | 0.75 | 1053.07 | HOTELSMALL ALWAYSOFF | 0.0 | 0.0 | 0.0000 | 0.0 |
| GUESTROOM306_308 ZN SMALLHOTEL GUESTROOM123VAC LIGHTS | GUESTROOM306_308 ZN | 0.75 | 850.56 | HOTELSMALL ALWAYSOFF | 0.0 | 0.0 | 0.0000 | 0.0 |
| GUESTROOM313 ZN SMALLHOTEL GUESTROOM123VAC LIGHTS | GUESTROOM313 ZN | 0.75 | 263.27 | HOTELSMALL ALWAYSOFF | 0.0 | 0.0 | 0.0000 | 0.0 |
| GUESTROOM319 ZN SMALLHOTEL GUESTROOM123VAC LIGHTS | GUESTROOM319 ZN | 0.75 | 263.25 | HOTELSMALL ALWAYSOFF | 0.0 | 0.0 | 0.0000 | 0.0 |
| GUESTROOM324 ZN SMALLHOTEL GUESTROOM123VAC LIGHTS | GUESTROOM324 ZN | 0.75 | 263.25 | HOTELSMALL ALWAYSOFF | 0.0 | 0.0 | 0.0000 | 0.0 |
| GUESTROOM401 ZN SMALLHOTEL GUESTROOM4OCC LIGHTS | GUESTROOM401 ZN | 0.75 | 263.27 | HOTELSMALL BLDG_LIGHT_GUESTROOM_SCH_2010 | 60.84 | 60.84 | 0.0000 | 836.11 |
| GUESTROOM409_412 ZN SMALLHOTEL GUESTROOM4OCC LIGHTS | GUESTROOM409_412 ZN | 0.75 | 1053.07 | HOTELSMALL BLDG_LIGHT_GUESTROOM_SCH_2010 | 60.84 | 60.84 | 0.0000 | 3341.67 |
| GUESTROOM415_418 ZN SMALLHOTEL GUESTROOM4OCC LIGHTS | GUESTROOM415_418 ZN | 0.75 | 1053.0 | HOTELSMALL BLDG_LIGHT_GUESTROOM_SCH_2010 | 60.84 | 60.84 | 0.0000 | 3338.89 |
| GUESTROOM419 ZN SMALLHOTEL GUESTROOM4OCC LIGHTS | GUESTROOM419 ZN | 0.75 | 263.25 | HOTELSMALL BLDG_LIGHT_GUESTROOM_SCH_2010 | 60.84 | 60.84 | 0.0000 | 836.11 |
| GUESTROOM420_423 ZN SMALLHOTEL GUESTROOM4OCC LIGHTS | GUESTROOM420_423 ZN | 0.75 | 1053.0 | HOTELSMALL BLDG_LIGHT_GUESTROOM_SCH_2010 | 60.84 | 60.84 | 0.0000 | 3338.89 |
| GUESTROOM424 ZN SMALLHOTEL GUESTROOM4OCC LIGHTS | GUESTROOM424 ZN | 0.75 | 263.25 | HOTELSMALL BLDG_LIGHT_GUESTROOM_SCH_2010 | 60.84 | 60.84 | 0.0000 | 836.11 |
| GUESTROOM402_405 ZN SMALLHOTEL GUESTROOM4VAC LIGHTS | GUESTROOM402_405 ZN | 0.75 | 1053.07 | HOTELSMALL ALWAYSOFF | 0.0 | 0.0 | 0.0000 | 0.0 |
| GUESTROOM406_408 ZN SMALLHOTEL GUESTROOM4VAC LIGHTS | GUESTROOM406_408 ZN | 0.75 | 850.56 | HOTELSMALL ALWAYSOFF | 0.0 | 0.0 | 0.0000 | 0.0 |
| GUESTROOM413 ZN SMALLHOTEL GUESTROOM4VAC LIGHTS | GUESTROOM413 ZN | 0.75 | 263.27 | HOTELSMALL ALWAYSOFF | 0.0 | 0.0 | 0.0000 | 0.0 |
| GUESTROOM414 ZN SMALLHOTEL GUESTROOM4VAC LIGHTS | GUESTROOM414 ZN | 0.75 | 263.25 | HOTELSMALL ALWAYSOFF | 0.0 | 0.0 | 0.0000 | 0.0 |
| LAUNDRYROOMFLR1 ZN SMALLHOTEL LAUNDRY LIGHTS | LAUNDRYROOMFLR1 ZN | 0.6 | 631.8 | HOTELSMALL BLDG_LIGHT_LAUNDRY_SCH | 63.0 | 63.0 | 0.0000 | 2075.0 |
| MECHANICALROOMFLR1 ZN SMALLHOTEL MECHANICAL LIGHTS | MECHANICALROOMFLR1 ZN | 0.95 | 333.47 | HOTELSMALL BLDG_LIGHT_MECHROOM_SCH | 41.3 | 41.3 | 0.0000 | 719.44 |
| MEETINGROOMFLR1 ZN SMALLHOTEL MEETING LIGHTS | MEETINGROOMFLR1 ZN | 1.23 | 1062.8 | HOTELSMALL BLDG_LIGHT_MEETINGROOM_SCH | 84.35 | 84.35 | 0.0000 | 4675.0 |
| FRONTOFFICEFLR1 ZN SMALLHOTEL OFFICE LIGHTS | FRONTOFFICEFLR1 ZN | 1.11 | 1558.44 | HOTELSMALL BLDG_LIGHT_OFFICE_SCH | 91.88 | 91.88 | 0.0000 | 7466.67 |
| RESTROOMFLR1 ZN SMALLHOTEL PUBLICRESTROOM LIGHTS | RESTROOMFLR1 ZN | 0.98 | 344.0 | HOTELSMALL BLDG_LIGHT_RESTROOM_SCH | 110.88 | 110.88 | 0.0000 | 1988.89 |
| EMPLOYEELOUNGEFLR1 ZN SMALLHOTEL STAFFLOUNGE LIGHTS | EMPLOYEELOUNGEFLR1 ZN | 0.73 | 256.23 | HOTELSMALL BLDG_LIGHT_EMPLOYEELOUNGE_SCH | 84.35 | 84.35 | 0.0000 | 1127.78 |
| FRONTSTAIRSFLR1 ZN SMALLHOTEL STAIR LIGHTS | FRONTSTAIRSFLR1 ZN | 0.69 | 149.04 | HOTELSMALL BLDG_LIGHT_STAIR_SCH | 92.4 | 92.4 | 0.0000 | 716.67 |
| FRONTSTAIRSFLR2 ZN SMALLHOTEL STAIR LIGHTS | FRONTSTAIRSFLR2 ZN | 0.69 | 149.04 | HOTELSMALL BLDG_LIGHT_STAIR_SCH | 92.4 | 92.4 | 0.0000 | 716.67 |
| FRONTSTAIRSFLR3 ZN SMALLHOTEL STAIR LIGHTS | FRONTSTAIRSFLR3 ZN | 0.69 | 149.04 | HOTELSMALL BLDG_LIGHT_STAIR_SCH | 92.4 | 92.4 | 0.0000 | 716.67 |
| REARSTAIRSFLR1 ZN SMALLHOTEL STAIR LIGHTS | REARSTAIRSFLR1 ZN | 0.69 | 149.08 | HOTELSMALL BLDG_LIGHT_STAIR_SCH | 92.4 | 92.4 | 0.0000 | 719.44 |
| REARSTAIRSFLR2 ZN SMALLHOTEL STAIR LIGHTS | REARSTAIRSFLR2 ZN | 0.69 | 149.08 | HOTELSMALL BLDG_LIGHT_STAIR_SCH | 92.4 | 92.4 | 0.0000 | 719.44 |
| REARSTAIRSFLR3 ZN SMALLHOTEL STAIR LIGHTS | REARSTAIRSFLR3 ZN | 0.69 | 149.08 | HOTELSMALL BLDG_LIGHT_STAIR_SCH | 92.4 | 92.4 | 0.0000 | 719.44 |
| FRONTSTAIRSFLR4 ZN SMALLHOTEL STAIR4 LIGHTS | FRONTSTAIRSFLR4 ZN | 0.69 | 149.04 | HOTELSMALL BLDG_LIGHT_STAIR_SCH | 92.4 | 92.4 | 0.0000 | 716.67 |
| REARSTAIRSFLR4 ZN SMALLHOTEL STAIR4 LIGHTS | REARSTAIRSFLR4 ZN | 0.69 | 149.08 | HOTELSMALL BLDG_LIGHT_STAIR_SCH | 92.4 | 92.4 | 0.0000 | 719.44 |
| FRONTSTORAGEFLR1 ZN SMALLHOTEL STORAGE LIGHTS | FRONTSTORAGEFLR1 ZN | 0.63 | 85.05 | HOTELSMALL BLDG_LIGHT_STORAGE_SCH | 22.38 | 22.38 | 0.0000 | 100.0 |
| FRONTSTORAGEFLR2 ZN SMALLHOTEL STORAGE LIGHTS | FRONTSTORAGEFLR2 ZN | 0.63 | 85.05 | HOTELSMALL BLDG_LIGHT_STORAGE_SCH | 22.38 | 22.38 | 0.0000 | 100.0 |
| FRONTSTORAGEFLR3 ZN SMALLHOTEL STORAGE LIGHTS | FRONTSTORAGEFLR3 ZN | 0.63 | 85.05 | HOTELSMALL BLDG_LIGHT_STORAGE_SCH | 22.38 | 22.38 | 0.0000 | 100.0 |
| REARSTORAGEFLR1 ZN SMALLHOTEL STORAGE LIGHTS | REARSTORAGEFLR1 ZN | 0.63 | 136.12 | HOTELSMALL BLDG_LIGHT_STORAGE_SCH | 22.38 | 22.38 | 0.0000 | 158.33 |
| REARSTORAGEFLR2 ZN SMALLHOTEL STORAGE LIGHTS | REARSTORAGEFLR2 ZN | 0.63 | 136.12 | HOTELSMALL BLDG_LIGHT_STORAGE_SCH | 22.38 | 22.38 | 0.0000 | 158.33 |
| REARSTORAGEFLR3 ZN SMALLHOTEL STORAGE LIGHTS | REARSTORAGEFLR3 ZN | 0.63 | 136.12 | HOTELSMALL BLDG_LIGHT_STORAGE_SCH | 22.38 | 22.38 | 0.0000 | 158.33 |
| FRONTSTORAGEFLR4 ZN SMALLHOTEL STORAGE4FRONT LIGHTS | FRONTSTORAGEFLR4 ZN | 0.63 | 85.05 | HOTELSMALL BLDG_LIGHT_STORAGE_SCH | 22.38 | 22.38 | 0.0000 | 100.0 |
| REARSTORAGEFLR4 ZN SMALLHOTEL STORAGE4REAR LIGHTS | REARSTORAGEFLR4 ZN | 0.63 | 136.12 | HOTELSMALL BLDG_LIGHT_STORAGE_SCH | 22.38 | 22.38 | 0.0000 | 158.33 |
Plug Loads Summary
| Electricity Annual Value (kWh) | |
|---|---|
| InteriorEquipment:Electricity:Zone:ELEVATORCOREFLR1 ZN | 69144.44 |
| InteriorEquipment:Electricity:Zone:EXERCISECENTERFLR1 ZN | 2327.78 |
| InteriorEquipment:Electricity:Zone:FRONTLOUNGEFLR1 ZN | 13983.33 |
| InteriorEquipment:Electricity:Zone:GUESTROOM103 ZN | 1161.11 |
| InteriorEquipment:Electricity:Zone:GUESTROOM104 ZN | 1161.11 |
| InteriorEquipment:Electricity:Zone:GUESTROOM105 ZN | 1161.11 |
| InteriorEquipment:Electricity:Zone:GUESTROOM202_205 ZN | 4647.22 |
| InteriorEquipment:Electricity:Zone:GUESTROOM206_208 ZN | 3752.78 |
| InteriorEquipment:Electricity:Zone:GUESTROOM209_212 ZN | 4647.22 |
| InteriorEquipment:Electricity:Zone:GUESTROOM213 ZN | 1161.11 |
| InteriorEquipment:Electricity:Zone:GUESTROOM214 ZN | 1161.11 |
| InteriorEquipment:Electricity:Zone:GUESTROOM219 ZN | 1161.11 |
| InteriorEquipment:Electricity:Zone:GUESTROOM220_223 ZN | 4647.22 |
| InteriorEquipment:Electricity:Zone:GUESTROOM224 ZN | 1161.11 |
| InteriorEquipment:Electricity:Zone:GUESTROOM309_312 ZN | 4647.22 |
| InteriorEquipment:Electricity:Zone:GUESTROOM314 ZN | 1161.11 |
| InteriorEquipment:Electricity:Zone:GUESTROOM315_318 ZN | 4647.22 |
| InteriorEquipment:Electricity:Zone:GUESTROOM320_323 ZN | 4647.22 |
| InteriorEquipment:Electricity:Zone:GUESTROOM101 ZN | 0.0 |
| InteriorEquipment:Electricity:Zone:GUESTROOM102 ZN | 0.0 |
| InteriorEquipment:Electricity:Zone:GUESTROOM201 ZN | 0.0 |
| InteriorEquipment:Electricity:Zone:GUESTROOM215_218 ZN | 0.0 |
| InteriorEquipment:Electricity:Zone:GUESTROOM301 ZN | 0.0 |
| InteriorEquipment:Electricity:Zone:GUESTROOM302_305 ZN | 0.0 |
| InteriorEquipment:Electricity:Zone:GUESTROOM306_308 ZN | 0.0 |
| InteriorEquipment:Electricity:Zone:GUESTROOM313 ZN | 0.0 |
| InteriorEquipment:Electricity:Zone:GUESTROOM319 ZN | 0.0 |
| InteriorEquipment:Electricity:Zone:GUESTROOM324 ZN | 0.0 |
| InteriorEquipment:Electricity:Zone:GUESTROOM401 ZN | 1161.11 |
| InteriorEquipment:Electricity:Zone:GUESTROOM409_412 ZN | 4647.22 |
| InteriorEquipment:Electricity:Zone:GUESTROOM415_418 ZN | 4647.22 |
| InteriorEquipment:Electricity:Zone:GUESTROOM419 ZN | 1161.11 |
| InteriorEquipment:Electricity:Zone:GUESTROOM420_423 ZN | 4647.22 |
| InteriorEquipment:Electricity:Zone:GUESTROOM424 ZN | 1161.11 |
| InteriorEquipment:Electricity:Zone:GUESTROOM402_405 ZN | 0.0 |
| InteriorEquipment:Electricity:Zone:GUESTROOM406_408 ZN | 0.0 |
| InteriorEquipment:Electricity:Zone:GUESTROOM413 ZN | 0.0 |
| InteriorEquipment:Electricity:Zone:GUESTROOM414 ZN | 0.0 |
| InteriorEquipment:Electricity:Zone:LAUNDRYROOMFLR1 ZN | 7902.78 |
| InteriorEquipment:Electricity:Zone:MEETINGROOMFLR1 ZN | 663.89 |
| InteriorEquipment:Electricity:Zone:FRONTOFFICEFLR1 ZN | 8880.56 |
| InteriorEquipment:Electricity:Zone:EMPLOYEELOUNGEFLR1 ZN | 2838.89 |
| Gas Annual Value (kBtu) | |
|---|---|
| InteriorEquipment:Gas:Zone:LAUNDRYROOMFLR1 ZN | 399410.13 |
Exterior Lighting
| Description | Total Power (W) | Annual Consumption (kWh) |
|---|---|---|
| Exterior Lighting Total | 4,188.00 | 1,028,636.11 |
Water Use Equipment
| Instance | Plant Loop | Definition | Space | Peak Flow Rate (gal/min) | Flow Rate Schedule | Target Temp Range (F) |
|---|---|---|---|---|---|---|
| Guestroom101 Service Water Use 0.04gal/min | Main Service Water Loop | Guestroom101 Service Water Use Def 0.04gal/min | 0.04 | HotelSmall AlwaysOff | 140.0 to 140.0 | |
| Guestroom102 Service Water Use 0.04gal/min | Main Service Water Loop | Guestroom102 Service Water Use Def 0.04gal/min | 0.04 | HotelSmall AlwaysOff | 140.0 to 140.0 | |
| Guestroom103 Service Water Use 0.04gal/min | Main Service Water Loop | Guestroom103 Service Water Use Def 0.04gal/min | 0.04 | HotelSmall GuestRoom_SHW_Sch | 140.0 to 140.0 | |
| Guestroom104 Service Water Use 0.04gal/min | Main Service Water Loop | Guestroom104 Service Water Use Def 0.04gal/min | 0.04 | HotelSmall GuestRoom_SHW_Sch | 140.0 to 140.0 | |
| Guestroom105 Service Water Use 0.04gal/min | Main Service Water Loop | Guestroom105 Service Water Use Def 0.04gal/min | 0.04 | HotelSmall GuestRoom_SHW_Sch | 140.0 to 140.0 | |
| Guestroom201 Service Water Use 0.04gal/min | Main Service Water Loop | Guestroom201 Service Water Use Def 0.04gal/min | 0.04 | HotelSmall AlwaysOff | 140.0 to 140.0 | |
| Guestroom202_205 Service Water Use 0.15gal/min | Main Service Water Loop | Guestroom202_205 Service Water Use Def 0.15gal/min | 0.15 | HotelSmall GuestRoom_SHW_Sch | 140.0 to 140.0 | |
| Guestroom206_208 Service Water Use 0.12gal/min | Main Service Water Loop | Guestroom206_208 Service Water Use Def 0.12gal/min | 0.12 | HotelSmall GuestRoom_SHW_Sch | 140.0 to 140.0 | |
| Guestroom209_212 Service Water Use 0.15gal/min | Main Service Water Loop | Guestroom209_212 Service Water Use Def 0.15gal/min | 0.15 | HotelSmall GuestRoom_SHW_Sch | 140.0 to 140.0 | |
| Guestroom213 Service Water Use 0.04gal/min | Main Service Water Loop | Guestroom213 Service Water Use Def 0.04gal/min | 0.04 | HotelSmall GuestRoom_SHW_Sch | 140.0 to 140.0 | |
| Guestroom214 Service Water Use 0.04gal/min | Main Service Water Loop | Guestroom214 Service Water Use Def 0.04gal/min | 0.04 | HotelSmall GuestRoom_SHW_Sch | 140.0 to 140.0 | |
| Guestroom215_218 Service Water Use 0.15gal/min | Main Service Water Loop | Guestroom215_218 Service Water Use Def 0.15gal/min | 0.15 | HotelSmall AlwaysOff | 140.0 to 140.0 | |
| Guestroom219 Service Water Use 0.04gal/min | Main Service Water Loop | Guestroom219 Service Water Use Def 0.04gal/min | 0.04 | HotelSmall GuestRoom_SHW_Sch | 140.0 to 140.0 | |
| Guestroom220_223 Service Water Use 0.15gal/min | Main Service Water Loop | Guestroom220_223 Service Water Use Def 0.15gal/min | 0.15 | HotelSmall GuestRoom_SHW_Sch | 140.0 to 140.0 | |
| Guestroom224 Service Water Use 0.04gal/min | Main Service Water Loop | Guestroom224 Service Water Use Def 0.04gal/min | 0.04 | HotelSmall GuestRoom_SHW_Sch | 140.0 to 140.0 | |
| Guestroom301 Service Water Use 0.04gal/min | Main Service Water Loop | Guestroom301 Service Water Use Def 0.04gal/min | 0.04 | HotelSmall AlwaysOff | 140.0 to 140.0 | |
| Guestroom302_305 Service Water Use 0.15gal/min | Main Service Water Loop | Guestroom302_305 Service Water Use Def 0.15gal/min | 0.15 | HotelSmall AlwaysOff | 140.0 to 140.0 | |
| Guestroom306_308 Service Water Use 0.12gal/min | Main Service Water Loop | Guestroom306_308 Service Water Use Def 0.12gal/min | 0.12 | HotelSmall AlwaysOff | 140.0 to 140.0 | |
| Guestroom309_312 Service Water Use 0.15gal/min | Main Service Water Loop | Guestroom309_312 Service Water Use Def 0.15gal/min | 0.15 | HotelSmall GuestRoom_SHW_Sch | 140.0 to 140.0 | |
| Guestroom313 Service Water Use 0.04gal/min | Main Service Water Loop | Guestroom313 Service Water Use Def 0.04gal/min | 0.04 | HotelSmall AlwaysOff | 140.0 to 140.0 | |
| Guestroom314 Service Water Use 0.04gal/min | Main Service Water Loop | Guestroom314 Service Water Use Def 0.04gal/min | 0.04 | HotelSmall GuestRoom_SHW_Sch | 140.0 to 140.0 | |
| Guestroom315_318 Service Water Use 0.15gal/min | Main Service Water Loop | Guestroom315_318 Service Water Use Def 0.15gal/min | 0.15 | HotelSmall GuestRoom_SHW_Sch | 140.0 to 140.0 | |
| Guestroom319 Service Water Use 0.04gal/min | Main Service Water Loop | Guestroom319 Service Water Use Def 0.04gal/min | 0.04 | HotelSmall AlwaysOff | 140.0 to 140.0 | |
| Guestroom320_323 Service Water Use 0.15gal/min | Main Service Water Loop | Guestroom320_323 Service Water Use Def 0.15gal/min | 0.15 | HotelSmall GuestRoom_SHW_Sch | 140.0 to 140.0 | |
| Guestroom324 Service Water Use 0.04gal/min | Main Service Water Loop | Guestroom324 Service Water Use Def 0.04gal/min | 0.04 | HotelSmall AlwaysOff | 140.0 to 140.0 | |
| Guestroom401 Service Water Use 0.04gal/min | Main Service Water Loop | Guestroom401 Service Water Use Def 0.04gal/min | 0.04 | HotelSmall GuestRoom_SHW_Sch | 140.0 to 140.0 | |
| Guestroom402_405 Service Water Use 0.15gal/min | Main Service Water Loop | Guestroom402_405 Service Water Use Def 0.15gal/min | 0.15 | HotelSmall AlwaysOff | 140.0 to 140.0 | |
| Guestroom406_408 Service Water Use 0.12gal/min | Main Service Water Loop | Guestroom406_408 Service Water Use Def 0.12gal/min | 0.12 | HotelSmall AlwaysOff | 140.0 to 140.0 | |
| Guestroom409_412 Service Water Use 0.15gal/min | Main Service Water Loop | Guestroom409_412 Service Water Use Def 0.15gal/min | 0.15 | HotelSmall GuestRoom_SHW_Sch | 140.0 to 140.0 | |
| Guestroom413 Service Water Use 0.04gal/min | Main Service Water Loop | Guestroom413 Service Water Use Def 0.04gal/min | 0.04 | HotelSmall AlwaysOff | 140.0 to 140.0 | |
| Guestroom414 Service Water Use 0.04gal/min | Main Service Water Loop | Guestroom414 Service Water Use Def 0.04gal/min | 0.04 | HotelSmall AlwaysOff | 140.0 to 140.0 | |
| Guestroom415_418 Service Water Use 0.15gal/min | Main Service Water Loop | Guestroom415_418 Service Water Use Def 0.15gal/min | 0.15 | HotelSmall GuestRoom_SHW_Sch | 140.0 to 140.0 | |
| Guestroom419 Service Water Use 0.04gal/min | Main Service Water Loop | Guestroom419 Service Water Use Def 0.04gal/min | 0.04 | HotelSmall GuestRoom_SHW_Sch | 140.0 to 140.0 | |
| Guestroom420_423 Service Water Use 0.15gal/min | Main Service Water Loop | Guestroom420_423 Service Water Use Def 0.15gal/min | 0.15 | HotelSmall GuestRoom_SHW_Sch | 140.0 to 140.0 | |
| Guestroom424 Service Water Use 0.04gal/min | Main Service Water Loop | Guestroom424 Service Water Use Def 0.04gal/min | 0.04 | HotelSmall GuestRoom_SHW_Sch | 140.0 to 140.0 | |
| Laundry Service Water Use 2.05gal/min | Laundry Service Water Loop | Laundry Service Water Use Def 2.05gal/min | 2.05 | HotelSmall LaundryRoom_SHW_Sch | 180.0 to 180.0 |
HVAC Load Profiles
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Average Outdoor Air Dry Bulb (F) | ||||||||||||
| Cooling Load (MBtu) | 16.26 | 12.95 | 20.36 | 26.01 | 34.81 | 47.43 | 54.21 | 55.17 | 42.34 | 28.81 | 18.87 | 15.73 |
| Heating Load (MBtu) | 30.87 | 36.11 | 26.34 | 9.35 | 4.06 | 0.29 | 0.07 | 0.02 | 0.88 | 7.27 | 25.06 | 35.55 |
Zone Conditions
| Zone | Unmet Htg (hr) | Unmet Htg - Occ (hr) | < 56 (F) | 56-61 (F) | 61-66 (F) | 66-68 (F) | 68-70 (F) | 70-72 (F) | 72-74 (F) | 74-76 (F) | 76-78 (F) | 78-83 (F) | 83-88 (F) | >= 88 (F) | Unmet Clg (hr) | Unmet Clg - Occ (hr) | Mean Temp (F) |
|---|
| Zone | < 30 (%) | 30-35 (%) | 35-40 (%) | 40-45 (%) | 45-50 (%) | 50-55 (%) | 55-60 (%) | 60-65 (%) | 65-70 (%) | 70-75 (%) | 75-80 (%) | >= 80 (%) | Mean Relative Humidity (%) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| CORRIDORFLR1 ZN | 7104 | 1089 | 411 | 116 | 29 | 8 | 3 | 0 | 0 | 0 | 0 | 0 | 20.4 (%) |
| CORRIDORFLR2 ZN | 6432 | 1285 | 916 | 127 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 21.3 (%) |
| CORRIDORFLR3 ZN | 6320 | 951 | 969 | 414 | 102 | 4 | 0 | 0 | 0 | 0 | 0 | 0 | 22.5 (%) |
| CORRIDORFLR4 ZN | 6246 | 998 | 941 | 408 | 146 | 21 | 0 | 0 | 0 | 0 | 0 | 0 | 22.8 (%) |
| ELEVATORCOREFLR1 ZN | 8760 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 2.9 (%) |
| ELEVATORCOREFLR2 ZN | 8616 | 123 | 21 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 13.6 (%) |
| ELEVATORCOREFLR3 ZN | 6839 | 840 | 624 | 342 | 66 | 49 | 0 | 0 | 0 | 0 | 0 | 0 | 20.8 (%) |
| ELEVATORCOREFLR4 ZN | 6363 | 792 | 696 | 514 | 250 | 101 | 37 | 7 | 0 | 0 | 0 | 0 | 23.4 (%) |
| EMPLOYEELOUNGEFLR1 ZN | 5276 | 1022 | 1003 | 894 | 412 | 122 | 27 | 4 | 0 | 0 | 0 | 0 | 27.2 (%) |
| EXERCISECENTERFLR1 ZN | 5052 | 1145 | 1056 | 1028 | 382 | 81 | 16 | 0 | 0 | 0 | 0 | 0 | 28.2 (%) |
| FRONTLOUNGEFLR1 ZN | 5112 | 982 | 888 | 762 | 491 | 297 | 130 | 71 | 23 | 4 | 0 | 0 | 28.9 (%) |
| FRONTOFFICEFLR1 ZN | 5002 | 1107 | 1162 | 1024 | 378 | 72 | 15 | 0 | 0 | 0 | 0 | 0 | 28.7 (%) |
| FRONTSTAIRSFLR1 ZN | 5952 | 878 | 755 | 581 | 324 | 181 | 60 | 29 | 0 | 0 | 0 | 0 | 25.5 (%) |
| FRONTSTAIRSFLR2 ZN | 6070 | 933 | 790 | 530 | 296 | 96 | 45 | 0 | 0 | 0 | 0 | 0 | 25.2 (%) |
| FRONTSTAIRSFLR3 ZN | 5970 | 1011 | 808 | 525 | 312 | 93 | 41 | 0 | 0 | 0 | 0 | 0 | 25.7 (%) |
| FRONTSTAIRSFLR4 ZN | 5772 | 1076 | 779 | 546 | 350 | 165 | 61 | 11 | 0 | 0 | 0 | 0 | 26.5 (%) |
| FRONTSTORAGEFLR1 ZN | 6322 | 687 | 755 | 570 | 306 | 72 | 48 | 0 | 0 | 0 | 0 | 0 | 23.9 (%) |
| FRONTSTORAGEFLR2 ZN | 6350 | 731 | 801 | 493 | 286 | 59 | 40 | 0 | 0 | 0 | 0 | 0 | 23.9 (%) |
| FRONTSTORAGEFLR3 ZN | 6285 | 795 | 834 | 472 | 280 | 55 | 39 | 0 | 0 | 0 | 0 | 0 | 24.3 (%) |
| FRONTSTORAGEFLR4 ZN | 6120 | 979 | 702 | 517 | 248 | 152 | 28 | 14 | 0 | 0 | 0 | 0 | 24.8 (%) |
| GUESTROOM101 ZN | 5852 | 727 | 770 | 653 | 399 | 233 | 81 | 43 | 2 | 0 | 0 | 0 | 25.7 (%) |
| GUESTROOM102 ZN | 5816 | 724 | 760 | 629 | 436 | 241 | 98 | 41 | 15 | 0 | 0 | 0 | 26.0 (%) |
| GUESTROOM103 ZN | 4865 | 1422 | 1548 | 841 | 83 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 28.3 (%) |
| GUESTROOM104 ZN | 4923 | 1485 | 1587 | 727 | 38 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 27.9 (%) |
| GUESTROOM105 ZN | 4955 | 1725 | 1727 | 352 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 27.4 (%) |
| GUESTROOM201 ZN | 5960 | 855 | 940 | 618 | 269 | 99 | 19 | 0 | 0 | 0 | 0 | 0 | 24.8 (%) |
| GUESTROOM202_205 ZN | 4910 | 1493 | 1629 | 701 | 27 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 27.9 (%) |
| GUESTROOM206_208 ZN | 4924 | 1517 | 1651 | 643 | 25 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 27.8 (%) |
| GUESTROOM209_212 ZN | 4915 | 1427 | 1558 | 799 | 61 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 28.0 (%) |
| GUESTROOM213 ZN | 4896 | 1505 | 1680 | 653 | 26 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 28.0 (%) |
| GUESTROOM214 ZN | 4943 | 1672 | 1738 | 404 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 27.5 (%) |
| GUESTROOM215_218 ZN | 6289 | 1783 | 676 | 12 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 21.2 (%) |
| GUESTROOM219 ZN | 5092 | 3473 | 195 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 26.2 (%) |
| GUESTROOM220_223 ZN | 4943 | 1564 | 1623 | 607 | 23 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 27.7 (%) |
| GUESTROOM224 ZN | 4940 | 1670 | 1739 | 408 | 3 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 27.5 (%) |
| GUESTROOM301 ZN | 5737 | 962 | 862 | 686 | 311 | 168 | 27 | 7 | 0 | 0 | 0 | 0 | 25.4 (%) |
| GUESTROOM302_305 ZN | 5708 | 945 | 814 | 709 | 329 | 197 | 37 | 21 | 0 | 0 | 0 | 0 | 25.6 (%) |
| GUESTROOM306_308 ZN | 5758 | 909 | 846 | 683 | 323 | 186 | 35 | 20 | 0 | 0 | 0 | 0 | 25.5 (%) |
| GUESTROOM309_312 ZN | 4912 | 1432 | 1558 | 799 | 59 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 28.0 (%) |
| GUESTROOM313 ZN | 5800 | 893 | 867 | 676 | 309 | 171 | 36 | 8 | 0 | 0 | 0 | 0 | 25.4 (%) |
| GUESTROOM314 ZN | 4930 | 1624 | 1721 | 477 | 8 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 27.6 (%) |
| GUESTROOM315_318 ZN | 4954 | 1660 | 1687 | 451 | 8 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 27.5 (%) |
| GUESTROOM319 ZN | 6274 | 1054 | 1043 | 347 | 42 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 22.2 (%) |
| GUESTROOM320_323 ZN | 4940 | 1521 | 1567 | 699 | 33 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 27.8 (%) |
| GUESTROOM324 ZN | 6067 | 803 | 889 | 605 | 278 | 95 | 23 | 0 | 0 | 0 | 0 | 0 | 24.2 (%) |
| GUESTROOM401 ZN | 4989 | 1465 | 1547 | 710 | 49 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 27.5 (%) |
| GUESTROOM402_405 ZN | 5681 | 995 | 895 | 644 | 335 | 169 | 28 | 13 | 0 | 0 | 0 | 0 | 25.4 (%) |
| GUESTROOM406_408 ZN | 5705 | 999 | 903 | 644 | 309 | 161 | 28 | 11 | 0 | 0 | 0 | 0 | 25.3 (%) |
| GUESTROOM409_412 ZN | 4895 | 1494 | 1543 | 761 | 67 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 27.9 (%) |
| GUESTROOM413 ZN | 5747 | 1024 | 961 | 615 | 259 | 130 | 23 | 1 | 0 | 0 | 0 | 0 | 25.1 (%) |
| GUESTROOM414 ZN | 5935 | 1005 | 969 | 547 | 215 | 74 | 15 | 0 | 0 | 0 | 0 | 0 | 24.3 (%) |
| GUESTROOM415_418 ZN | 4921 | 1591 | 1578 | 638 | 32 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 27.7 (%) |
| GUESTROOM419 ZN | 4927 | 1700 | 1710 | 416 | 7 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 27.5 (%) |
| GUESTROOM420_423 ZN | 4912 | 1585 | 1550 | 667 | 46 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 27.8 (%) |
| GUESTROOM424 ZN | 4912 | 1660 | 1715 | 463 | 10 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 27.6 (%) |
| LAUNDRYROOMFLR1 ZN | 4729 | 822 | 740 | 728 | 667 | 540 | 333 | 151 | 44 | 6 | 0 | 0 | 26.5 (%) |
| MECHANICALROOMFLR1 ZN | 6264 | 682 | 823 | 620 | 327 | 44 | 0 | 0 | 0 | 0 | 0 | 0 | 24.0 (%) |
| MEETINGROOMFLR1 ZN | 5024 | 1013 | 890 | 821 | 552 | 278 | 135 | 36 | 11 | 0 | 0 | 0 | 28.5 (%) |
| REARSTAIRSFLR1 ZN | 5907 | 805 | 713 | 631 | 360 | 217 | 80 | 47 | 0 | 0 | 0 | 0 | 25.5 (%) |
| REARSTAIRSFLR2 ZN | 6029 | 876 | 741 | 581 | 307 | 148 | 53 | 25 | 0 | 0 | 0 | 0 | 25.1 (%) |
| REARSTAIRSFLR3 ZN | 5962 | 923 | 759 | 578 | 308 | 157 | 52 | 21 | 0 | 0 | 0 | 0 | 25.5 (%) |
| REARSTAIRSFLR4 ZN | 5743 | 1016 | 779 | 562 | 366 | 198 | 69 | 27 | 0 | 0 | 0 | 0 | 26.4 (%) |
| REARSTORAGEFLR1 ZN | 5690 | 824 | 740 | 652 | 423 | 250 | 114 | 48 | 19 | 0 | 0 | 0 | 26.7 (%) |
| REARSTORAGEFLR2 ZN | 5665 | 915 | 735 | 695 | 385 | 233 | 83 | 49 | 0 | 0 | 0 | 0 | 26.8 (%) |
| REARSTORAGEFLR3 ZN | 5433 | 1071 | 787 | 711 | 403 | 237 | 71 | 47 | 0 | 0 | 0 | 0 | 27.6 (%) |
| REARSTORAGEFLR4 ZN | 5220 | 1128 | 841 | 675 | 472 | 231 | 133 | 45 | 15 | 0 | 0 | 0 | 28.4 (%) |
| RESTROOMFLR1 ZN | 5472 | 1115 | 1183 | 671 | 245 | 59 | 15 | 0 | 0 | 0 | 0 | 0 | 26.5 (%) |
Zone Overview
| Area (ft^2) | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume (ft^3) | Multiplier | Above Ground Gross Wall Area (ft^2) | Underground Gross Wall Area (ft^2) | Window Glass Area (ft^2) | Lighting (W/ft^2) | People (ft^2/person) | Plug and Process (W/ft^2) | |
|---|---|---|---|---|---|---|---|---|---|---|---|
| CORRIDORFLR1 ZN | 1620.08 | Yes | Yes | 17820.49 | 1.00 | 351.98 | 0.0 | 105.7 | 0.66 | 0.0 | 0.0 |
| CORRIDORFLR2 ZN | 1350.01 | Yes | Yes | 12150.01 | 1.00 | 197.95 | 0.0 | 28.2 | 0.66 | 0.0 | 0.0 |
| CORRIDORFLR3 ZN | 1350.01 | Yes | Yes | 12150.01 | 1.00 | 197.95 | 0.0 | 28.2 | 0.66 | 0.0 | 0.0 |
| CORRIDORFLR4 ZN | 1350.01 | Yes | Yes | 12150.01 | 1.00 | 197.95 | 0.0 | 28.2 | 0.66 | 0.0 | 0.0 |
| ELEVATORCOREFLR1 ZN | 162.0 | No | Yes | 1781.98 | 1.00 | 65.98 | 0.0 | 0.0 | 0.0 | 0.0 | 198.2 |
| ELEVATORCOREFLR2 ZN | 162.0 | No | Yes | 1458.14 | 1.00 | 54.03 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| ELEVATORCOREFLR3 ZN | 162.0 | No | Yes | 1458.14 | 1.00 | 54.03 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| ELEVATORCOREFLR4 ZN | 162.0 | No | Yes | 1458.14 | 1.00 | 54.03 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| EMPLOYEELOUNGEFLR1 ZN | 351.01 | Yes | Yes | 3860.95 | 1.00 | 143.05 | 0.0 | 17.76 | 0.73 | 19.48 | 2.0 |
| EXERCISECENTERFLR1 ZN | 351.01 | Yes | Yes | 3860.95 | 1.00 | 143.05 | 0.0 | 17.76 | 0.72 | 50.16 | 1.73 |
| FRONTLOUNGEFLR1 ZN | 1755.16 | Yes | Yes | 19306.53 | 1.00 | 1012.02 | 0.0 | 159.63 | 0.73 | 33.37 | 2.42 |
| FRONTOFFICEFLR1 ZN | 1404.04 | Yes | Yes | 15444.16 | 1.00 | 571.99 | 0.0 | 70.83 | 1.11 | 140.04 | 1.28 |
| FRONTSTAIRSFLR1 ZN | 216.03 | Yes | Yes | 2375.97 | 1.00 | 385.03 | 0.0 | 0.0 | 0.69 | 0.0 | 0.0 |
| FRONTSTAIRSFLR2 ZN | 216.03 | Yes | Yes | 1944.07 | 1.00 | 314.95 | 0.0 | 0.0 | 0.69 | 0.0 | 0.0 |
| FRONTSTAIRSFLR3 ZN | 216.03 | Yes | Yes | 1944.07 | 1.00 | 314.95 | 0.0 | 0.0 | 0.69 | 0.0 | 0.0 |
| FRONTSTAIRSFLR4 ZN | 216.03 | Yes | Yes | 1944.07 | 1.00 | 314.95 | 0.0 | 0.0 | 0.69 | 0.0 | 0.0 |
| FRONTSTORAGEFLR1 ZN | 134.98 | No | Yes | 1484.98 | 1.00 | 55.0 | 0.0 | 0.0 | 0.63 | 0.0 | 0.0 |
| FRONTSTORAGEFLR2 ZN | 134.98 | No | Yes | 1214.82 | 1.00 | 44.99 | 0.0 | 0.0 | 0.63 | 0.0 | 0.0 |
| FRONTSTORAGEFLR3 ZN | 134.98 | No | Yes | 1214.82 | 1.00 | 44.99 | 0.0 | 0.0 | 0.63 | 0.0 | 0.0 |
| FRONTSTORAGEFLR4 ZN | 134.98 | No | Yes | 1214.82 | 1.00 | 44.99 | 0.0 | 0.0 | 0.63 | 0.0 | 0.0 |
| GUESTROOM101 ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 234.22 | 1.1 |
| GUESTROOM102 ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 234.22 | 1.1 |
| GUESTROOM103 ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 234.22 | 1.1 |
| GUESTROOM104 ZN | 351.01 | Yes | Yes | 3860.95 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 234.22 | 1.1 |
| GUESTROOM105 ZN | 351.01 | Yes | Yes | 3860.95 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 234.22 | 1.1 |
| GUESTROOM201 ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 360.05 | 0.0 | 17.76 | 0.75 | 234.22 | 1.1 |
| GUESTROOM202_205 ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 234.22 | 1.1 |
| GUESTROOM206_208 ZN | 1134.09 | Yes | Yes | 10206.64 | 1.00 | 378.03 | 0.0 | 72.12 | 0.75 | 234.22 | 1.1 |
| GUESTROOM209_212 ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 234.22 | 1.1 |
| GUESTROOM213 ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 234.22 | 1.1 |
| GUESTROOM214 ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 234.22 | 1.1 |
| GUESTROOM215_218 ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 234.22 | 1.1 |
| GUESTROOM219 ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 234.22 | 1.1 |
| GUESTROOM220_223 ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 234.22 | 1.1 |
| GUESTROOM224 ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 234.22 | 1.1 |
| GUESTROOM301 ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 360.05 | 0.0 | 17.76 | 0.75 | 234.22 | 1.1 |
| GUESTROOM302_305 ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 234.22 | 1.1 |
| GUESTROOM306_308 ZN | 1134.09 | Yes | Yes | 10206.64 | 1.00 | 378.03 | 0.0 | 72.12 | 0.75 | 234.22 | 1.1 |
| GUESTROOM309_312 ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 234.22 | 1.1 |
| GUESTROOM313 ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 234.22 | 1.1 |
| GUESTROOM314 ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 234.22 | 1.1 |
| GUESTROOM315_318 ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 234.22 | 1.1 |
| GUESTROOM319 ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 234.22 | 1.1 |
| GUESTROOM320_323 ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 234.22 | 1.1 |
| GUESTROOM324 ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 234.22 | 1.1 |
| GUESTROOM401 ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 360.05 | 0.0 | 17.76 | 0.75 | 234.22 | 1.1 |
| GUESTROOM402_405 ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 234.22 | 1.1 |
| GUESTROOM406_408 ZN | 1134.09 | Yes | Yes | 10206.64 | 1.00 | 378.03 | 0.0 | 72.12 | 0.75 | 234.22 | 1.1 |
| GUESTROOM409_412 ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 234.22 | 1.1 |
| GUESTROOM413 ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 234.22 | 1.1 |
| GUESTROOM414 ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 234.22 | 1.1 |
| GUESTROOM415_418 ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 234.22 | 1.1 |
| GUESTROOM419 ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 234.22 | 1.1 |
| GUESTROOM420_423 ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 234.22 | 1.1 |
| GUESTROOM424 ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 234.22 | 1.1 |
| LAUNDRYROOMFLR1 ZN | 1053.03 | No | Yes | 11582.86 | 1.00 | 429.05 | 0.0 | 53.17 | 0.6 | 100.0 | 40.64 |
| MECHANICALROOMFLR1 ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 0.0 | 0.95 | 0.0 | 0.0 |
| MEETINGROOMFLR1 ZN | 864.02 | Yes | Yes | 9504.59 | 1.00 | 351.98 | 0.0 | 53.17 | 1.23 | 20.02 | 0.57 |
| REARSTAIRSFLR1 ZN | 216.03 | Yes | Yes | 2376.68 | 1.00 | 385.03 | 0.0 | 0.0 | 0.69 | 0.0 | 0.0 |
| REARSTAIRSFLR2 ZN | 216.03 | Yes | Yes | 1944.43 | 1.00 | 315.06 | 0.0 | 0.0 | 0.69 | 0.0 | 0.0 |
| REARSTAIRSFLR3 ZN | 216.03 | Yes | Yes | 1944.43 | 1.00 | 315.06 | 0.0 | 0.0 | 0.69 | 0.0 | 0.0 |
| REARSTAIRSFLR4 ZN | 216.03 | Yes | Yes | 1944.43 | 1.00 | 315.06 | 0.0 | 0.0 | 0.69 | 0.0 | 0.0 |
| REARSTORAGEFLR1 ZN | 216.03 | No | Yes | 2376.68 | 1.00 | 385.03 | 0.0 | 0.0 | 0.63 | 0.0 | 0.0 |
| REARSTORAGEFLR2 ZN | 216.03 | No | Yes | 1944.78 | 1.00 | 315.06 | 0.0 | 0.0 | 0.63 | 0.0 | 0.0 |
| REARSTORAGEFLR3 ZN | 216.03 | No | Yes | 1944.78 | 1.00 | 315.06 | 0.0 | 0.0 | 0.63 | 0.0 | 0.0 |
| REARSTORAGEFLR4 ZN | 216.03 | No | Yes | 1944.78 | 1.00 | 315.06 | 0.0 | 0.0 | 0.63 | 0.0 | 0.0 |
| RESTROOMFLR1 ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 0.0 | 0.98 | 350.9 | 0.0 |
| Total | 43201.82 | 410417.54 | 18240.31 | 0.0 | 1982.71 | 0.74 | 166.84 | 2.61 | |||
| Conditioned Total | 40096.54 | 379337.8 | 16063.2 | 0.0 | 1929.54 | 0.76 | 161.46 | 0.94 | |||
| Unconditioned Total | 3105.28 | 31079.38 | 2177.11 | 0.0 | 53.17 | 0.49 | 294.93 | 24.12 | |||
| Not Part of Total | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| Heating/Cooling | Calculated Design Load | Design Load With Sizing Factor | Calculated Design Air Flow (ft^3/min) | Design Air Flow With Sizing Factor (ft^3/min) | Date/Time Of Peak | Outdoor Temperature at Peak Load (F) | Outdoor Humidity Ratio at Peak Load (lbWater/lbAir) | |
|---|---|---|---|---|---|---|---|---|
| EMPLOYEELOUNGEFLR1 ZN | Cooling | 1.53 (ton) | 1.83 (ton) | 1169.62 | 1404.82 | 7/21 14:15:00 | 91.4 | 0.01 |
| EMPLOYEELOUNGEFLR1 ZN | Heating | 1.3 (kBtu/h) | 1.56 (kBtu/h) | 27.55 | 156.8 | 12/21 08:00:00 | -1.84 | 0.0 |
| EXERCISECENTERFLR1 ZN | Cooling | 0.33 (ton) | 0.39 (ton) | 252.15 | 303.0 | 7/21 17:00:00 | 87.57 | 0.01 |
| EXERCISECENTERFLR1 ZN | Heating | 0.77 (kBtu/h) | 0.92 (kBtu/h) | 16.95 | 161.03 | 12/21 06:00:00 | -1.84 | 0.0 |
| FRONTLOUNGEFLR1 ZN | Cooling | 2.03 (ton) | 2.43 (ton) | 1555.26 | 1864.61 | 7/21 15:15:00 | 90.99 | 0.01 |
| FRONTLOUNGEFLR1 ZN | Heating | 6.82 (kBtu/h) | 8.19 (kBtu/h) | 148.32 | 500.06 | 12/21 07:00:00 | -1.84 | 0.0 |
| FRONTOFFICEFLR1 ZN | Cooling | 0.86 (ton) | 1.03 (ton) | 658.97 | 790.34 | 7/21 14:15:00 | 91.4 | 0.01 |
| FRONTOFFICEFLR1 ZN | Heating | 4.1 (kBtu/h) | 4.92 (kBtu/h) | 88.99 | 133.49 | 12/21 06:15:00 | -1.84 | 0.0 |
| GUESTROOM101 ZN | Cooling | 0.05 (ton) | 0.06 (ton) | 40.26 | 48.73 | 7/21 15:30:00 | 90.57 | 0.01 |
| GUESTROOM101 ZN | Heating | 0.28 (kBtu/h) | 0.33 (kBtu/h) | 6.36 | 27.55 | 12/21 07:15:00 | -1.84 | 0.0 |
| GUESTROOM102 ZN | Cooling | 0.04 (ton) | 0.04 (ton) | 29.66 | 36.02 | 7/21 15:30:00 | 90.57 | 0.01 |
| GUESTROOM102 ZN | Heating | 0.26 (kBtu/h) | 0.32 (kBtu/h) | 6.36 | 27.55 | 12/21 07:15:00 | -1.84 | 0.0 |
| GUESTROOM103 ZN | Cooling | 0.3 (ton) | 0.36 (ton) | 317.83 | 381.4 | 7/21 18:15:00 | 83.8 | 0.01 |
| GUESTROOM103 ZN | Heating | 2.12 (kBtu/h) | 2.54 (kBtu/h) | 46.62 | 55.09 | 12/21 07:15:00 | -1.84 | 0.0 |
| GUESTROOM104 ZN | Cooling | 0.32 (ton) | 0.39 (ton) | 343.26 | 411.06 | 7/21 14:30:00 | 91.4 | 0.01 |
| GUESTROOM104 ZN | Heating | 1.86 (kBtu/h) | 2.23 (kBtu/h) | 40.26 | 48.73 | 12/21 07:45:00 | -1.84 | 0.0 |
| GUESTROOM105 ZN | Cooling | 0.45 (ton) | 0.53 (ton) | 474.63 | 567.86 | 7/21 14:15:00 | 91.4 | 0.01 |
| GUESTROOM105 ZN | Heating | 1.28 (kBtu/h) | 1.53 (kBtu/h) | 27.55 | 33.9 | 12/21 08:30:00 | -1.84 | 0.0 |
| GUESTROOM201 ZN | Cooling | 0.13 (ton) | 0.16 (ton) | 108.06 | 131.37 | 7/21 14:45:00 | 91.4 | 0.01 |
| GUESTROOM201 ZN | Heating | 1.12 (kBtu/h) | 1.35 (kBtu/h) | 23.31 | 27.55 | 12/21 10:45:00 | -1.84 | 0.0 |
| GUESTROOM202_205 ZN | Cooling | 1.22 (ton) | 1.47 (ton) | 1300.99 | 1561.61 | 7/21 15:30:00 | 90.57 | 0.01 |
| GUESTROOM202_205 ZN | Heating | 4.95 (kBtu/h) | 5.94 (kBtu/h) | 108.06 | 129.25 | 12/21 10:15:00 | -1.84 | 0.0 |
| GUESTROOM206_208 ZN | Cooling | 0.99 (ton) | 1.19 (ton) | 1055.2 | 1264.97 | 7/21 15:30:00 | 90.57 | 0.01 |
| GUESTROOM206_208 ZN | Heating | 3.8 (kBtu/h) | 4.56 (kBtu/h) | 82.64 | 99.59 | 12/21 08:45:00 | -1.84 | 0.0 |
| GUESTROOM209_212 ZN | Cooling | 1.11 (ton) | 1.33 (ton) | 1180.22 | 1417.53 | 7/21 15:30:00 | 90.57 | 0.01 |
| GUESTROOM209_212 ZN | Heating | 4.24 (kBtu/h) | 5.08 (kBtu/h) | 93.23 | 114.42 | 12/21 09:00:00 | -1.84 | 0.0 |
| GUESTROOM213 ZN | Cooling | 0.33 (ton) | 0.39 (ton) | 347.5 | 417.42 | 7/21 18:30:00 | 82.78 | 0.01 |
| GUESTROOM213 ZN | Heating | 2.33 (kBtu/h) | 2.79 (kBtu/h) | 50.85 | 61.45 | 12/21 10:45:00 | -1.84 | 0.0 |
| GUESTROOM214 ZN | Cooling | 0.38 (ton) | 0.46 (ton) | 406.82 | 489.46 | 7/21 14:30:00 | 91.4 | 0.01 |
| GUESTROOM214 ZN | Heating | 2.11 (kBtu/h) | 2.53 (kBtu/h) | 46.62 | 55.09 | 12/21 10:00:00 | -1.84 | 0.0 |
| GUESTROOM215_218 ZN | Cooling | 2.33 (ton) | 2.8 (ton) | 1892.16 | 2271.44 | 7/21 14:15:00 | 91.4 | 0.01 |
| GUESTROOM215_218 ZN | Heating | 1.21 (kBtu/h) | 1.45 (kBtu/h) | 25.43 | 114.42 | 12/21 09:00:00 | -1.84 | 0.0 |
| GUESTROOM219 ZN | Cooling | 1.57 (ton) | 1.88 (ton) | 1669.68 | 2002.34 | 7/21 14:30:00 | 91.4 | 0.01 |
| GUESTROOM219 ZN | Heating | 1.28 (kBtu/h) | 1.53 (kBtu/h) | 27.55 | 33.9 | 12/21 09:00:00 | -1.84 | 0.0 |
| GUESTROOM220_223 ZN | Cooling | 1.28 (ton) | 1.53 (ton) | 1360.32 | 1631.54 | 7/21 14:15:00 | 91.4 | 0.01 |
| GUESTROOM220_223 ZN | Heating | 3.51 (kBtu/h) | 4.21 (kBtu/h) | 76.28 | 114.42 | 12/21 08:00:00 | -1.84 | 0.0 |
| GUESTROOM224 ZN | Cooling | 0.38 (ton) | 0.45 (ton) | 402.59 | 483.1 | 7/21 14:15:00 | 91.4 | 0.01 |
| GUESTROOM224 ZN | Heating | 1.82 (kBtu/h) | 2.18 (kBtu/h) | 40.26 | 46.62 | 12/21 09:00:00 | -1.84 | 0.0 |
| GUESTROOM301 ZN | Cooling | 0.11 (ton) | 0.13 (ton) | 86.87 | 103.83 | 7/21 15:00:00 | 91.4 | 0.01 |
| GUESTROOM301 ZN | Heating | 1.42 (kBtu/h) | 1.71 (kBtu/h) | 29.66 | 33.9 | 12/21 16:45:00 | -1.84 | 0.0 |
| GUESTROOM302_305 ZN | Cooling | 0.24 (ton) | 0.29 (ton) | 197.06 | 237.31 | 7/21 15:45:00 | 90.18 | 0.01 |
| GUESTROOM302_305 ZN | Heating | 2.68 (kBtu/h) | 3.21 (kBtu/h) | 55.09 | 114.42 | 12/21 16:30:00 | -1.84 | 0.0 |
| GUESTROOM306_308 ZN | Cooling | 0.21 (ton) | 0.25 (ton) | 169.51 | 203.41 | 7/21 15:45:00 | 90.18 | 0.01 |
| GUESTROOM306_308 ZN | Heating | 2.17 (kBtu/h) | 2.6 (kBtu/h) | 44.5 | 93.23 | 12/21 12:45:00 | -1.84 | 0.0 |
| GUESTROOM309_312 ZN | Cooling | 1.12 (ton) | 1.35 (ton) | 1195.05 | 1432.36 | 7/21 15:45:00 | 90.18 | 0.01 |
| GUESTROOM309_312 ZN | Heating | 4.91 (kBtu/h) | 5.89 (kBtu/h) | 108.06 | 129.25 | 12/21 13:00:00 | -1.84 | 0.0 |
| GUESTROOM313 ZN | Cooling | 0.09 (ton) | 0.11 (ton) | 74.16 | 86.87 | 7/21 18:15:00 | 83.8 | 0.01 |
| GUESTROOM313 ZN | Heating | 1.53 (kBtu/h) | 1.84 (kBtu/h) | 31.78 | 38.14 | 12/21 23:00:00 | -1.84 | 0.0 |
| GUESTROOM314 ZN | Cooling | 0.36 (ton) | 0.44 (ton) | 385.64 | 464.03 | 7/21 14:45:00 | 91.4 | 0.01 |
| GUESTROOM314 ZN | Heating | 2.49 (kBtu/h) | 2.99 (kBtu/h) | 55.09 | 65.69 | 12/21 15:30:00 | -1.84 | 0.0 |
| GUESTROOM315_318 ZN | Cooling | 1.49 (ton) | 1.79 (ton) | 1589.16 | 1906.99 | 7/21 14:30:00 | 91.4 | 0.01 |
| GUESTROOM315_318 ZN | Heating | 5.11 (kBtu/h) | 6.14 (kBtu/h) | 112.3 | 133.49 | 12/21 12:45:00 | -1.84 | 0.0 |
| GUESTROOM319 ZN | Cooling | 0.21 (ton) | 0.25 (ton) | 169.51 | 203.41 | 7/21 14:30:00 | 91.4 | 0.01 |
| GUESTROOM319 ZN | Heating | 0.35 (kBtu/h) | 0.42 (kBtu/h) | 6.36 | 27.55 | 12/21 13:15:00 | -1.84 | 0.0 |
| GUESTROOM320_323 ZN | Cooling | 1.24 (ton) | 1.49 (ton) | 1317.94 | 1582.8 | 7/21 14:30:00 | 91.4 | 0.01 |
| GUESTROOM320_323 ZN | Heating | 4.36 (kBtu/h) | 5.24 (kBtu/h) | 95.35 | 114.42 | 12/21 12:45:00 | -1.84 | 0.0 |
| GUESTROOM324 ZN | Cooling | 0.11 (ton) | 0.13 (ton) | 84.76 | 101.71 | 7/21 14:30:00 | 91.4 | 0.01 |
| GUESTROOM324 ZN | Heating | 0.92 (kBtu/h) | 1.11 (kBtu/h) | 19.07 | 27.55 | 12/21 19:45:00 | -1.84 | 0.0 |
| GUESTROOM401 ZN | Cooling | 0.45 (ton) | 0.53 (ton) | 474.63 | 569.98 | 7/21 14:00:00 | 91.4 | 0.01 |
| GUESTROOM401 ZN | Heating | 3.46 (kBtu/h) | 4.15 (kBtu/h) | 76.28 | 91.11 | 12/21 22:00:00 | -1.84 | 0.0 |
| GUESTROOM402_405 ZN | Cooling | 0.5 (ton) | 0.6 (ton) | 404.71 | 485.22 | 7/21 14:30:00 | 91.4 | 0.01 |
| GUESTROOM402_405 ZN | Heating | 6.21 (kBtu/h) | 7.45 (kBtu/h) | 125.01 | 150.44 | 12/21 21:15:00 | -1.84 | 0.0 |
| GUESTROOM406_408 ZN | Cooling | 0.42 (ton) | 0.51 (ton) | 343.26 | 413.18 | 7/21 14:30:00 | 91.4 | 0.01 |
| GUESTROOM406_408 ZN | Heating | 5.18 (kBtu/h) | 6.21 (kBtu/h) | 105.94 | 125.01 | 12/21 18:45:00 | -1.84 | 0.0 |
| GUESTROOM409_412 ZN | Cooling | 1.45 (ton) | 1.74 (ton) | 1542.54 | 1851.9 | 7/21 14:30:00 | 91.4 | 0.01 |
| GUESTROOM409_412 ZN | Heating | 8.29 (kBtu/h) | 9.94 (kBtu/h) | 180.1 | 216.13 | 12/21 19:30:00 | -1.84 | 0.0 |
| GUESTROOM413 ZN | Cooling | 0.17 (ton) | 0.2 (ton) | 137.73 | 165.27 | 7/21 15:15:00 | 90.99 | 0.01 |
| GUESTROOM413 ZN | Heating | 2.73 (kBtu/h) | 3.27 (kBtu/h) | 55.09 | 65.69 | 12/21 23:30:00 | -1.84 | 0.0 |
| GUESTROOM414 ZN | Cooling | 0.2 (ton) | 0.24 (ton) | 161.03 | 192.82 | 7/21 14:30:00 | 91.4 | 0.01 |
| GUESTROOM414 ZN | Heating | 2.36 (kBtu/h) | 2.83 (kBtu/h) | 48.73 | 57.21 | 12/21 21:15:00 | -1.84 | 0.0 |
| GUESTROOM415_418 ZN | Cooling | 1.64 (ton) | 1.97 (ton) | 1748.08 | 2095.57 | 7/21 13:45:00 | 91.06 | 0.01 |
| GUESTROOM415_418 ZN | Heating | 8.03 (kBtu/h) | 9.63 (kBtu/h) | 175.87 | 209.77 | 12/21 16:45:00 | -1.84 | 0.0 |
| GUESTROOM419 ZN | Cooling | 0.46 (ton) | 0.55 (ton) | 491.58 | 589.05 | 7/21 14:00:00 | 91.4 | 0.01 |
| GUESTROOM419 ZN | Heating | 2.47 (kBtu/h) | 2.97 (kBtu/h) | 52.97 | 65.69 | 12/21 17:45:00 | -1.84 | 0.0 |
| GUESTROOM420_423 ZN | Cooling | 1.6 (ton) | 1.92 (ton) | 1703.58 | 2044.72 | 7/21 13:45:00 | 91.06 | 0.01 |
| GUESTROOM420_423 ZN | Heating | 7.59 (kBtu/h) | 9.11 (kBtu/h) | 165.27 | 199.17 | 12/21 19:00:00 | -1.84 | 0.0 |
| GUESTROOM424 ZN | Cooling | 0.46 (ton) | 0.55 (ton) | 491.58 | 589.05 | 7/21 14:15:00 | 91.4 | 0.01 |
| GUESTROOM424 ZN | Heating | 3.22 (kBtu/h) | 3.86 (kBtu/h) | 69.92 | 84.76 | 12/21 23:15:00 | -1.84 | 0.0 |
| MEETINGROOMFLR1 ZN | Cooling | 0.98 (ton) | 1.17 (ton) | 750.08 | 900.52 | 7/21 15:00:00 | 91.4 | 0.01 |
| MEETINGROOMFLR1 ZN | Heating | 2.6 (kBtu/h) | 3.12 (kBtu/h) | 57.21 | 266.98 | 12/21 07:00:00 | -1.84 | 0.0 |
| RESTROOMFLR1 ZN | Cooling | 0.11 (ton) | 0.14 (ton) | 88.99 | 105.94 | 7/21 16:00:00 | 89.76 | 0.01 |
| RESTROOMFLR1 ZN | Heating | 0.51 (kBtu/h) | 0.62 (kBtu/h) | 10.59 | 21.19 | 12/21 07:15:00 | -1.84 | 0.0 |
| CORRIDORFLR1 ZN | Cooling | 4.23 (ton) | 5.07 (ton) | 3237.65 | 3883.91 | 7/21 18:00:00 | 84.83 | 0.01 |
| CORRIDORFLR1 ZN | Heating | 94.55 (kBtu/h) | 113.47 (kBtu/h) | 2063.79 | 2474.85 | 12/21 08:00:00 | -1.84 | 0.0 |
| CORRIDORFLR2 ZN | Cooling | 0.77 (ton) | 0.93 (ton) | 593.29 | 711.94 | 7/21 16:45:00 | 88.12 | 0.01 |
| CORRIDORFLR2 ZN | Heating | 3.52 (kBtu/h) | 4.22 (kBtu/h) | 76.28 | 91.11 | 12/21 09:30:00 | -1.84 | 0.0 |
| CORRIDORFLR3 ZN | Cooling | 0.42 (ton) | 0.51 (ton) | 324.19 | 387.76 | 7/21 17:00:00 | 87.57 | 0.01 |
| CORRIDORFLR3 ZN | Heating | 5.0 (kBtu/h) | 6.0 (kBtu/h) | 110.18 | 131.37 | 12/21 13:45:00 | -1.84 | 0.0 |
| CORRIDORFLR4 ZN | Cooling | 0.69 (ton) | 0.83 (ton) | 527.6 | 633.55 | 7/21 15:00:00 | 91.4 | 0.01 |
| CORRIDORFLR4 ZN | Heating | 9.32 (kBtu/h) | 11.19 (kBtu/h) | 203.41 | 243.67 | 12/21 23:45:00 | -1.84 | 0.0 |
| FRONTSTAIRSFLR1 ZN | Cooling | 0.0 (ton) | 0.0 (ton) | 0.0 | 12.71 | 91.4 | 0.01 | |
| FRONTSTAIRSFLR1 ZN | Heating | 0.0 (kBtu/h) | 0.0 (kBtu/h) | 0.0 | 12.71 | -1.84 | 0.0 | |
| FRONTSTAIRSFLR2 ZN | Cooling | 0.0 (ton) | 0.0 (ton) | 0.0 | 12.71 | 91.4 | 0.01 | |
| FRONTSTAIRSFLR2 ZN | Heating | 0.0 (kBtu/h) | 0.0 (kBtu/h) | 0.0 | 12.71 | -1.84 | 0.0 | |
| FRONTSTAIRSFLR3 ZN | Cooling | 0.0 (ton) | 0.0 (ton) | 0.0 | 12.71 | 91.4 | 0.01 | |
| FRONTSTAIRSFLR3 ZN | Heating | 0.0 (kBtu/h) | 0.0 (kBtu/h) | 0.0 | 12.71 | -1.84 | 0.0 | |
| FRONTSTAIRSFLR4 ZN | Cooling | 0.0 (ton) | 0.0 (ton) | 0.0 | 12.71 | 91.4 | 0.01 | |
| FRONTSTAIRSFLR4 ZN | Heating | 0.5 (kBtu/h) | 0.6 (kBtu/h) | 6.36 | 12.71 | 12/21 23:45:00 | -1.84 | 0.0 |
| MECHANICALROOMFLR1 ZN | Cooling | 0.0 (ton) | 0.0 (ton) | 0.0 | 42.38 | 91.4 | 0.01 | |
| MECHANICALROOMFLR1 ZN | Heating | 0.0 (kBtu/h) | 0.0 (kBtu/h) | 0.0 | 42.38 | -1.84 | 0.0 | |
| REARSTAIRSFLR1 ZN | Cooling | 0.0 (ton) | 0.0 (ton) | 0.0 | 12.71 | 91.4 | 0.01 | |
| REARSTAIRSFLR1 ZN | Heating | 0.0 (kBtu/h) | 0.0 (kBtu/h) | 0.0 | 12.71 | -1.84 | 0.0 | |
| REARSTAIRSFLR2 ZN | Cooling | 0.0 (ton) | 0.0 (ton) | 0.0 | 12.71 | 91.4 | 0.01 | |
| REARSTAIRSFLR2 ZN | Heating | 0.0 (kBtu/h) | 0.0 (kBtu/h) | 0.0 | 12.71 | -1.84 | 0.0 | |
| REARSTAIRSFLR3 ZN | Cooling | 0.0 (ton) | 0.0 (ton) | 0.0 | 12.71 | 91.4 | 0.01 | |
| REARSTAIRSFLR3 ZN | Heating | 0.0 (kBtu/h) | 0.0 (kBtu/h) | 0.0 | 12.71 | -1.84 | 0.0 | |
| REARSTAIRSFLR4 ZN | Cooling | 0.0 (ton) | 0.0 (ton) | 0.0 | 12.71 | 91.4 | 0.01 | |
| REARSTAIRSFLR4 ZN | Heating | 0.0 (kBtu/h) | 0.0 (kBtu/h) | 0.0 | 12.71 | -1.84 | 0.0 |
Zone Equipment Detail
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:UnitHeater |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:UnitHeater |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:UnitHeater |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:UnitHeater |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 1.33 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:UnitHeater |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:UnitHeater |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:UnitHeater |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:UnitHeater |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:UnitHeater |
Air Loops Detail
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | Autosized | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.65 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.50 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | ExerciseCenterFlr1 ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 1,053 | ft^2 | 3 | ||
| Thermal Zones | thermostat ranges for cooling | 75.0 to 75.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 70.0 to 70.0 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 3 | ||||
(controls) |
||||||
| HVAC Operation Schedule | SmallHotel Split-AC Operation | |||||
| Night Cycle Setting | CycleOnAny | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | Autosized | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.65 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.50 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | FrontLoungeFlr1 ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 1,755 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.0 to 75.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 70.0 to 70.0 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | SmallHotel Split-AC Operation | |||||
| Night Cycle Setting | CycleOnAny | Choice | ||||
| Economizer Setting | DifferentialDryBulb | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | Autosized | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.65 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.50 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | FrontOfficeFlr1 ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 1,404 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.0 to 75.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 70.0 to 70.0 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | Autosized | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.65 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.50 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | MeetingRoomFlr1 ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 864 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.0 to 75.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 70.0 to 70.0 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
Plant Loops Detail
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:Pump:ConstantSpeed | Autosized | gal/min | Rated Power Consumption | Autosized | W | |
| OS:WaterHeater:Mixed | 200 | gal | Heater Thermal Efficiency | 0.81 | fraction | |
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 140.0 to 140.0 | F | |||
(demand) |
||||||
| OS:WaterUse:Connections | Water Use Connections 36 | |||||
(controls) |
||||||
| Loop Flow Rate Range | Autosized | gal/min | Minimum Loop Flow Rate | 0.0 | gal/min | |
| Loop Temperature Range | 50.0 to 140.0 | F | ||||
| Design Loop Exit Temperature | 140.00 | F | ||||
| Loop Design Temperature Difference | 9.00 | R |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:Pump:ConstantSpeed | Autosized | gal/min | Rated Power Consumption | Autosized | W | |
| OS:WaterHeater:Mixed | 300 | gal | Heater Thermal Efficiency | 0.81 | fraction | |
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 140.0 to 140.0 | F | |||
(demand) |
||||||
| OS:WaterUse:Connections | Water Use Connections 1 | |||||
| OS:WaterUse:Connections | Water Use Connections 2 | |||||
| OS:WaterUse:Connections | Water Use Connections 3 | |||||
| OS:WaterUse:Connections | Water Use Connections 4 | |||||
| OS:WaterUse:Connections | Water Use Connections 5 | |||||
| OS:WaterUse:Connections | Water Use Connections 6 | |||||
| OS:WaterUse:Connections | Water Use Connections 7 | |||||
| OS:WaterUse:Connections | Water Use Connections 8 | |||||
| OS:WaterUse:Connections | Water Use Connections 9 | |||||
| OS:WaterUse:Connections | Water Use Connections 10 | |||||
| OS:WaterUse:Connections | Water Use Connections 11 | |||||
| OS:WaterUse:Connections | Water Use Connections 12 | |||||
| OS:WaterUse:Connections | Water Use Connections 13 | |||||
| OS:WaterUse:Connections | Water Use Connections 14 | |||||
| OS:WaterUse:Connections | Water Use Connections 15 | |||||
| OS:WaterUse:Connections | Water Use Connections 16 | |||||
| OS:WaterUse:Connections | Water Use Connections 17 | |||||
| OS:WaterUse:Connections | Water Use Connections 18 | |||||
| OS:WaterUse:Connections | Water Use Connections 19 | |||||
| OS:WaterUse:Connections | Water Use Connections 20 | |||||
| OS:WaterUse:Connections | Water Use Connections 21 | |||||
| OS:WaterUse:Connections | Water Use Connections 22 | |||||
| OS:WaterUse:Connections | Water Use Connections 23 | |||||
| OS:WaterUse:Connections | Water Use Connections 24 | |||||
| OS:WaterUse:Connections | Water Use Connections 25 | |||||
| OS:WaterUse:Connections | Water Use Connections 26 | |||||
| OS:WaterUse:Connections | Water Use Connections 27 | |||||
| OS:WaterUse:Connections | Water Use Connections 28 | |||||
| OS:WaterUse:Connections | Water Use Connections 29 | |||||
| OS:WaterUse:Connections | Water Use Connections 30 | |||||
| OS:WaterUse:Connections | Water Use Connections 31 | |||||
| OS:WaterUse:Connections | Water Use Connections 32 | |||||
| OS:WaterUse:Connections | Water Use Connections 33 | |||||
| OS:WaterUse:Connections | Water Use Connections 34 | |||||
| OS:WaterUse:Connections | Water Use Connections 35 | |||||
(controls) |
||||||
| Loop Flow Rate Range | Autosized | gal/min | Minimum Loop Flow Rate | 0.0 | gal/min | |
| Loop Temperature Range | 50.0 to 140.0 | F | ||||
| Design Loop Exit Temperature | 140.00 | F | ||||
| Loop Design Temperature Difference | 9.00 | R |
Outdoor Air
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume (ft^3) | Avg. Mechanical Ventilation (ach) | Min. Mechanical Ventilation (ach) | Avg. Infiltration (ach) | Min. Infiltration (ach) | Avg. Simple Ventilation (ach) | Min. Simple Ventilation (ach) | |
|---|---|---|---|---|---|---|---|---|---|
| EMPLOYEELOUNGEFLR1 ZN | 4.71 | 18.0 | 3861 | 4.073 | 3.925 | 0.029 | 0.0 | 0.0 | 0.0 |
| EXERCISECENTERFLR1 ZN | 6.34 | 7.0 | 3861 | 0.882 | 0.857 | 0.029 | 0.0 | 0.0 | 0.0 |
| FRONTLOUNGEFLR1 ZN | 16.57 | 52.65 | 19307 | 2.183 | 1.512 | 0.039 | 0.0 | 0.0 | 0.0 |
| FRONTOFFICEFLR1 ZN | 4.89 | 10.02 | 15444 | 0.525 | 0.51 | 0.028 | 0.0 | 0.0 | 0.0 |
| GUESTROOM101 ZN | 0.0 | 1.5 | 3861 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| GUESTROOM102 ZN | 0.0 | 1.5 | 3861 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| GUESTROOM103 ZN | 0.98 | 1.5 | 3861 | 0.444 | 0.432 | 0.028 | 0.0 | 0.0 | 0.0 |
| GUESTROOM104 ZN | 0.98 | 1.5 | 3861 | 0.444 | 0.433 | 0.028 | 0.0 | 0.0 | 0.0 |
| GUESTROOM105 ZN | 0.98 | 1.5 | 3861 | 0.444 | 0.433 | 0.028 | 0.0 | 0.0 | 0.0 |
| GUESTROOM201 ZN | 0.0 | 1.5 | 3159 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| GUESTROOM202_205 ZN | 3.93 | 6.0 | 12637 | 0.542 | 0.529 | 0.035 | 0.0 | 0.0 | 0.0 |
| GUESTROOM206_208 ZN | 3.18 | 4.84 | 10207 | 0.542 | 0.529 | 0.035 | 0.0 | 0.0 | 0.0 |
| GUESTROOM209_212 ZN | 3.93 | 6.0 | 12637 | 0.542 | 0.529 | 0.035 | 0.0 | 0.0 | 0.0 |
| GUESTROOM213 ZN | 0.98 | 1.5 | 3159 | 0.542 | 0.529 | 0.035 | 0.0 | 0.0 | 0.0 |
| GUESTROOM214 ZN | 0.98 | 1.5 | 3159 | 0.542 | 0.529 | 0.035 | 0.0 | 0.0 | 0.0 |
| GUESTROOM215_218 ZN | 0.0 | 6.0 | 12636 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| GUESTROOM219 ZN | 0.98 | 1.5 | 3159 | 0.542 | 0.529 | 0.035 | 0.0 | 0.0 | 0.0 |
| GUESTROOM220_223 ZN | 3.93 | 6.0 | 12636 | 0.542 | 0.529 | 0.035 | 0.0 | 0.0 | 0.0 |
| GUESTROOM224 ZN | 0.98 | 1.5 | 3159 | 0.542 | 0.529 | 0.035 | 0.0 | 0.0 | 0.0 |
| GUESTROOM301 ZN | 0.0 | 1.5 | 3159 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| GUESTROOM302_305 ZN | 0.0 | 6.0 | 12637 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| GUESTROOM306_308 ZN | 0.0 | 4.84 | 10207 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| GUESTROOM309_312 ZN | 3.93 | 6.0 | 12637 | 0.542 | 0.529 | 0.039 | 0.0 | 0.0 | 0.0 |
| GUESTROOM313 ZN | 0.0 | 1.5 | 3159 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| GUESTROOM314 ZN | 0.98 | 1.5 | 3159 | 0.542 | 0.529 | 0.039 | 0.0 | 0.0 | 0.0 |
| GUESTROOM315_318 ZN | 3.93 | 6.0 | 12636 | 0.542 | 0.529 | 0.039 | 0.0 | 0.0 | 0.0 |
| GUESTROOM319 ZN | 0.0 | 1.5 | 3159 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| GUESTROOM320_323 ZN | 3.93 | 6.0 | 12636 | 0.542 | 0.529 | 0.039 | 0.0 | 0.0 | 0.0 |
| GUESTROOM324 ZN | 0.0 | 1.5 | 3159 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| GUESTROOM401 ZN | 0.98 | 1.5 | 3159 | 0.542 | 0.527 | 0.127 | 0.0 | 0.0 | 0.0 |
| GUESTROOM402_405 ZN | 0.0 | 6.0 | 12637 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| GUESTROOM406_408 ZN | 0.0 | 4.84 | 10207 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| GUESTROOM409_412 ZN | 3.93 | 6.0 | 12637 | 0.542 | 0.529 | 0.041 | 0.0 | 0.0 | 0.0 |
| GUESTROOM413 ZN | 0.0 | 1.5 | 3159 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| GUESTROOM414 ZN | 0.0 | 1.5 | 3159 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| GUESTROOM415_418 ZN | 3.93 | 6.0 | 12636 | 0.542 | 0.529 | 0.041 | 0.0 | 0.0 | 0.0 |
| GUESTROOM419 ZN | 0.98 | 1.5 | 3159 | 0.542 | 0.529 | 0.041 | 0.0 | 0.0 | 0.0 |
| GUESTROOM420_423 ZN | 3.93 | 6.0 | 12636 | 0.542 | 0.529 | 0.041 | 0.0 | 0.0 | 0.0 |
| GUESTROOM424 ZN | 0.98 | 1.5 | 3159 | 0.542 | 0.529 | 0.041 | 0.0 | 0.0 | 0.0 |
| MEETINGROOMFLR1 ZN | 14.65 | 43.2 | 9505 | 1.695 | 1.645 | 0.029 | 0.0 | 0.0 | 0.0 |
| RESTROOMFLR1 ZN | 0.31 | 1.0 | 3861 | 0.307 | 0.298 | 0.028 | 0.0 | 0.0 | 0.0 |
Cash Flow
No Data to Show for Cash Flow
Site and Source Summary
| Total Energy (kBtu) | Energy Per Total Building Area (kBtu/ft^2) | Energy Per Conditioned Building Area (kBtu/ft^2) | |
|---|---|---|---|
| Total Site Energy | 3509852.2 | 81.2 | 87.5 |
| Net Site Energy | 3509852.2 | 81.2 | 87.5 |
| Total Source Energy | 8825257.6 | 204.3 | 220.1 |
| Net Source Energy | 8825257.6 | 204.3 | 220.1 |
| Site=>Source Conversion Factor | |
|---|---|
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
Schedule Overview
| Schedule | Type Limits | Rules | Use Count |
|---|---|---|---|
| Air Velocity Schedule | Velocity | 0 | 11 |
| Always On | Dimensionless | 0 | 75 |
| Clothing Schedule | ClothingInsulation | 1 | 11 |
| Fraction Latent - 0.05 | 0 | 1 | |
| Fraction Sensible - 0.2 | 0 | 1 | |
| HotelSmall Activity_Sch | ActivityLevel | 0 | 63 |
| HotelSmall Adva_OccGuestRoom_ClgSP_Sch | Temperature | 0 | 23 |
| HotelSmall Adva_OccGuestRoom_HtgSP_Sch | Temperature | 0 | 23 |
| HotelSmall AlwaysOff | Dimensionless | 0 | 53 |
| HotelSmall BLDG_ELEVATORS | Dimensionless | 0 | 4 |
| HotelSmall BLDG_LIGHT_CORRIDOR_SCH | Dimensionless | 0 | 4 |
| HotelSmall BLDG_LIGHT_EMPLOYEELOUNGE_SCH | Dimensionless | 0 | 1 |
| HotelSmall BLDG_LIGHT_EXERCENTER_SCH | Dimensionless | 0 | 1 |
| HotelSmall BLDG_LIGHT_FRONTLOUNGE_SCH | Dimensionless | 0 | 1 |
| HotelSmall BLDG_LIGHT_GUESTROOM_SCH_2010 | Dimensionless | 1 | 21 |
| HotelSmall BLDG_LIGHT_LAUNDRY_SCH | Dimensionless | 0 | 1 |
| HotelSmall BLDG_LIGHT_MECHROOM_SCH | Dimensionless | 1 | 1 |
| HotelSmall BLDG_LIGHT_MEETINGROOM_SCH | Dimensionless | 0 | 1 |
| HotelSmall BLDG_LIGHT_OFFICE_SCH | Dimensionless | 0 | 1 |
| HotelSmall BLDG_LIGHT_RESTROOM_SCH | Dimensionless | 0 | 1 |
| HotelSmall BLDG_LIGHT_STAIR_SCH | Dimensionless | 0 | 8 |
| HotelSmall BLDG_LIGHT_STORAGE_SCH | Dimensionless | 1 | 8 |
| HotelSmall CommonArea_ClgSP_Sch | Temperature | 0 | 20 |
| HotelSmall CommonArea_HtgSP_Sch | Temperature | 0 | 20 |
| HotelSmall CommonArea_Infil_Sch | Dimensionless | 0 | 16 |
| HotelSmall EmployeeLounge_Eqp_Sch | Dimensionless | 1 | 1 |
| HotelSmall EmployeeLounge_Occ_Sch | Dimensionless | 1 | 1 |
| HotelSmall ExerciseCenter_Eqp_Sch | Dimensionless | 0 | 1 |
| HotelSmall ExerciseCenter_Occ_Sch | Dimensionless | 0 | 1 |
| HotelSmall Exterior_Lgt_ALWAYS_ON | Dimensionless | 0 | 1 |
| HotelSmall GuestRoom_Eqp_Sch_Base | Dimensionless | 1 | 21 |
| HotelSmall GuestRoom_Infil_Sch | Dimensionless | 0 | 70 |
| HotelSmall GuestRoom_Occ_Sch | Dimensionless | 1 | 21 |
| HotelSmall GuestRoom_SHW_Sch | Dimensionless | 1 | 21 |
| HotelSmall INFIL_Door_Opening_SCH | Dimensionless | 0 | 1 |
| HotelSmall LaundryRoom_Eqp_Elec_Sch | Dimensionless | 0 | 1 |
| HotelSmall LaundryRoom_Eqp_Gas_Sch | Dimensionless | 0 | 1 |
| HotelSmall LaundryRoom_Occ_Sch | Dimensionless | 1 | 1 |
| HotelSmall LaundryRoom_SHW_Sch | Dimensionless | 0 | 1 |
| HotelSmall Lobby_Eqp_Sch | Dimensionless | 0 | 2 |
| HotelSmall Lobby_Occ_Sch | Dimensionless | 1 | 2 |
| HotelSmall MeetingRoom_Eqp_Sch | Dimensionless | 0 | 1 |
| HotelSmall MeetingRoom_Occ_Sch | Dimensionless | 1 | 1 |
| HotelSmall Office_Occ_Sch | Dimensionless | 1 | 1 |
| HotelSmall OFF_EQUIP_SCH | Dimensionless | 1 | 1 |
| HotelSmall SAC_Econ_MaxOAFrac_Sch | Dimensionless | 0 | 4 |
| HotelSmall SemiHeated_HtgSP_Sch | Temperature | 0 | 23 |
| HotelSmall VacGuestRoom_ClgSP_Sch | Temperature | 0 | 16 |
| HotelSmall VacGuestRoom_HtgSP_Sch | Temperature | 0 | 16 |
| Mixed Water At Faucet Temp - 180F | 0 | 1 | |
| Schedule Ruleset 10 | 0 | 1 | |
| Schedule Ruleset 100 | 0 | 1 | |
| Schedule Ruleset 101 | 0 | 1 | |
| Schedule Ruleset 102 | 0 | 1 | |
| Schedule Ruleset 103 | 0 | 1 | |
| Schedule Ruleset 104 | 0 | 1 | |
| Schedule Ruleset 105 | 0 | 1 | |
| Schedule Ruleset 106 | 0 | 1 | |
| Schedule Ruleset 107 | 0 | 1 | |
| Schedule Ruleset 11 | 0 | 1 | |
| Schedule Ruleset 12 | 0 | 1 | |
| Schedule Ruleset 13 | 0 | 1 | |
| Schedule Ruleset 14 | 0 | 1 | |
| Schedule Ruleset 15 | 0 | 1 | |
| Schedule Ruleset 16 | 0 | 1 | |
| Schedule Ruleset 17 | 0 | 1 | |
| Schedule Ruleset 18 | 0 | 1 | |
| Schedule Ruleset 19 | 0 | 1 | |
| Schedule Ruleset 20 | 0 | 1 | |
| Schedule Ruleset 21 | 0 | 1 | |
| Schedule Ruleset 22 | 0 | 1 | |
| Schedule Ruleset 23 | 0 | 1 | |
| Schedule Ruleset 24 | 0 | 1 | |
| Schedule Ruleset 25 | 0 | 1 | |
| Schedule Ruleset 26 | 0 | 1 | |
| Schedule Ruleset 27 | 0 | 1 | |
| Schedule Ruleset 28 | 0 | 1 | |
| Schedule Ruleset 29 | 0 | 1 | |
| Schedule Ruleset 3 | 0 | 1 | |
| Schedule Ruleset 30 | 0 | 1 | |
| Schedule Ruleset 31 | 0 | 1 | |
| Schedule Ruleset 32 | 0 | 1 | |
| Schedule Ruleset 33 | 0 | 1 | |
| Schedule Ruleset 34 | 0 | 1 | |
| Schedule Ruleset 35 | 0 | 1 | |
| Schedule Ruleset 36 | 0 | 1 | |
| Schedule Ruleset 37 | 0 | 1 | |
| Schedule Ruleset 38 | 0 | 1 | |
| Schedule Ruleset 39 | 0 | 1 | |
| Schedule Ruleset 4 | 0 | 1 | |
| Schedule Ruleset 40 | 0 | 1 | |
| Schedule Ruleset 41 | 0 | 1 | |
| Schedule Ruleset 42 | 0 | 1 | |
| Schedule Ruleset 43 | 0 | 1 | |
| Schedule Ruleset 44 | 0 | 1 | |
| Schedule Ruleset 45 | 0 | 1 | |
| Schedule Ruleset 46 | 0 | 1 | |
| Schedule Ruleset 47 | 0 | 1 | |
| Schedule Ruleset 48 | 0 | 1 | |
| Schedule Ruleset 49 | 0 | 1 | |
| Schedule Ruleset 5 | 0 | 1 | |
| Schedule Ruleset 50 | 0 | 1 | |
| Schedule Ruleset 51 | 0 | 1 | |
| Schedule Ruleset 52 | 0 | 1 | |
| Schedule Ruleset 53 | 0 | 1 | |
| Schedule Ruleset 54 | 0 | 1 | |
| Schedule Ruleset 55 | 0 | 1 | |
| Schedule Ruleset 56 | 0 | 1 | |
| Schedule Ruleset 57 | 0 | 1 | |
| Schedule Ruleset 58 | 0 | 1 | |
| Schedule Ruleset 59 | 0 | 1 | |
| Schedule Ruleset 6 | 0 | 1 | |
| Schedule Ruleset 60 | 0 | 1 | |
| Schedule Ruleset 61 | 0 | 1 | |
| Schedule Ruleset 62 | 0 | 1 | |
| Schedule Ruleset 63 | 0 | 1 | |
| Schedule Ruleset 64 | 0 | 1 | |
| Schedule Ruleset 65 | 0 | 1 | |
| Schedule Ruleset 66 | 0 | 1 | |
| Schedule Ruleset 67 | 0 | 1 | |
| Schedule Ruleset 68 | 0 | 1 | |
| Schedule Ruleset 69 | 0 | 1 | |
| Schedule Ruleset 7 | 0 | 1 | |
| Schedule Ruleset 70 | 0 | 1 | |
| Schedule Ruleset 71 | 0 | 1 | |
| Schedule Ruleset 72 | 0 | 1 | |
| Schedule Ruleset 73 | 0 | 1 | |
| Schedule Ruleset 74 | 0 | 1 | |
| Schedule Ruleset 75 | 0 | 1 | |
| Schedule Ruleset 76 | 0 | 1 | |
| Schedule Ruleset 77 | 0 | 1 | |
| Schedule Ruleset 78 | 0 | 1 | |
| Schedule Ruleset 79 | 0 | 1 | |
| Schedule Ruleset 8 | 0 | 1 | |
| Schedule Ruleset 80 | 0 | 1 | |
| Schedule Ruleset 81 | 0 | 1 | |
| Schedule Ruleset 82 | 0 | 1 | |
| Schedule Ruleset 83 | 0 | 1 | |
| Schedule Ruleset 84 | 0 | 1 | |
| Schedule Ruleset 85 | 0 | 1 | |
| Schedule Ruleset 86 | 0 | 1 | |
| Schedule Ruleset 87 | 0 | 1 | |
| Schedule Ruleset 88 | 0 | 1 | |
| Schedule Ruleset 89 | 0 | 1 | |
| Schedule Ruleset 9 | 0 | 1 | |
| Schedule Ruleset 90 | 0 | 1 | |
| Schedule Ruleset 91 | 0 | 1 | |
| Schedule Ruleset 92 | 0 | 1 | |
| Schedule Ruleset 93 | 0 | 1 | |
| Schedule Ruleset 94 | 0 | 1 | |
| Schedule Ruleset 95 | 0 | 1 | |
| Schedule Ruleset 96 | 0 | 1 | |
| Schedule Ruleset 97 | 0 | 1 | |
| Schedule Ruleset 98 | 0 | 1 | |
| Schedule Ruleset 99 | 0 | 1 | |
| Service Water Loop Temp - 140F | Temperature | 0 | 2 |
| Service Water Loop Temp - 140F 1 | Temperature | 0 | 2 |
| SmallHotel Split-AC Operation | Dimensionless | 0 | 4 |
| SmallHotel UnitHeater ClgSP Sch | Temperature | 0 | 23 |
| Water Heater Ambient Temp Schedule - 70F | Temperature | 0 | 1 |
| Water Heater Ambient Temp Schedule - 70F 1 | Temperature | 0 | 1 |
| Work Efficiency Schedule | Dimensionless | 0 | 11 |